active for the duration of the set pulse length. When activated, the additional
activation command does not extend the length of pulse. Thus, the pulse needs
to be ended before the new activation can occur.
The
Description setting can be used for storing signal names for each output.
Each control point or SPCLGAPC can only be accessed through the LHMI control.
SPCLGAPC follows the local or remote (L/R) state if the
Loc Rem restriction setting
is "true". If the
Loc Rem restriction setting is "false", local or remote (L/R) state is
ignored, that is, all controls are allowed regardless of the local or remote state.
The
BLOCK
input can be used for blocking the output functionality. The
BLOCK
input
operation depends on the
Operation mode setting. If the Operation mode setting is
set to "Toggle", the output state cannot be changed when the input
BLOCK
is TRUE.
If the
Operation mode setting is set to "Pulsed", the activation of the
BLOCK
input
resets the output to the FALSE state.
3.17.14.4
Signals
Table 201: SPCLGAPC Input signals
Name
Type
Default
Description
BLOCK
BOOLEAN
0=False
Block signal for acti-
vating the blocking
mode
Table 202: SPCLGAPC Output signals
Name
Type
Description
O1
BOOLEAN
Output 1 status
O2
BOOLEAN
Output 2 status
O3
BOOLEAN
Output 3 status
O4
BOOLEAN
Output 4 status
O5
BOOLEAN
Output 5 status
O6
BOOLEAN
Output 6 status
O7
BOOLEAN
Output 7 status
O8
BOOLEAN
Output 8 status
O9
BOOLEAN
Output 9 status
O10
BOOLEAN
Output 10 status
O11
BOOLEAN
Output 11 status
O12
BOOLEAN
Output 12 status
O13
BOOLEAN
Output 13 status
O14
BOOLEAN
Output 14 status
O15
BOOLEAN
Output 15 status
O16
BOOLEAN
Output 16 status
Basic functions
1MRS758755 C
184
REC615 & RER615
Technical Manual