6.4.6
Signals
Table 569: PHSVPR Input signals
Name
Type
Default
Description
U_A_AB
SIGNAL
0
Phase-to-earth voltage A or phase-to-
phase voltage AB
U_B_BC
SIGNAL
0
Phase-to-earth voltage B or phase-to-
phase voltage BC
U_C_CA
SIGNAL
0
Phase-to-earth voltage C or phase-to-
phase voltage CA
BLOCK
BOOLEAN
0=False
Block signal for activating the blocking
mode
Table 570: PHSVPR Output signals
Name
Type
Description
U_LIVE
BOOLEAN
Indicate high voltage presence
U_A_AB_LIVE
BOOLEAN
Indicate high phase to earth voltage A or phase to
phase voltage AB
U_B_BC_LIVE
BOOLEAN
Indicate high phase to earth voltage B or phase to
phase voltage BC
U_C_CA_LIVE
BOOLEAN
Indicate high phase to earth voltage C or phase to
phase voltage CA
U_DEAD
BOOLEAN
Indicate low voltage presence
U_A_AB_DEAD
BOOLEAN
Indicate low phase to earth voltage A or phase to
phase voltage AB
U_B_BC_DEAD
BOOLEAN
Indicate low phase to earth voltage B or phase to
phase voltage BC
U_C_CA_DEAD
BOOLEAN
Indicate low phase to earth voltage C or phase to
phase voltage CA
6.4.7
Settings
Table 571: PHSVPR Non group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=on
5=off
1=on
Operation Off /
On
Voltage selec-
tion
1=phase-to-earth
2=phase-to-phase Parameter to se-
lect phase or
Table continues on the next page
1MRS758755 C
Supervision functions
REC615 & RER615
Technical Manual
549