![ABB Relion REC615 Скачать руководство пользователя страница 118](http://html.mh-extra.com/html/abb/relion-rec615/relion-rec615_technical-manual_3045253118.webp)
3.14.4.1
Function block
Figure 46: Function block
3.14.4.2
Functionality
The RESTVTR function is used in the receiver application to perform the supervision
for the sampled values of analog residual voltage and to connect the received
analog residual voltage input to the application. Synchronization accuracy, sampled
value frame transfer delays and missing frames are being supervised.
The typical additional operate time increase is +2 ms for all the receiver
application functions (using either local or remote samples) when SMV is
used.
3.14.4.3
Operation principle
The
ALARM
in the receiver is activated if the synchronization accuracy of the sender
or the receiver is either unknown or worse than 100 ms. The output is held on for 10
seconds after the synchronization accuracy returns within limits.
ALARM
is activated when two or more consecutive SMV frames are lost or late. A
single loss of frame is corrected with a zero-order hold scheme. In this case, the
effect on protection is considered negligible and the
WARNING
or
ALARM
outputs are
not activated. The output is held on for 10 seconds after the conditions return to
normal.
The
SMV Max Delay parameter defines how long the receiver waits for the SMV
frames before activating the
ALARM
output. This parameter can be accessed via
Configuration/System/Common. Waiting of the SMV frames also delays the local
measurements of the receiver to keep them correctly time aligned. The
SMV Max
Delay values include sampling, processing and network delay.
The
WARNING
output in the receiver is activated if the synchronization accuracy of
the sender or the receiver is worse than 4 μs. The output is held on for 10 seconds
after the synchronization accuracy returns within limits.
The
WARNING
output is always internally active whenever the
ALARM
output is active.
3.14.4.4
Signals
Table 68: RESTVTR Input signals
Name
Type
Default
Description
Uo
INT32-UL0
0
IEC61850-9-2 residual
voltage
Basic functions
1MRS758755 C
118
REC615 & RER615
Technical Manual