INCA MODEL 

 
 

PSJ2 

 
 

PRESSURE 

CONTROLLER 

 
 

USER MANUAL 

 

Inca Reference PSJ2 

 

Software Version 1.0 

 

 
 
 
 
 
 
 
 
 
 
 
 
 

Technical Support 

Pumps & Mechanicals 

–  

Controls 

– Inca Control & Engineering Pty Ltd 

Phone 02 9632 2837 

 

 
 

 

 

Summary of Contents for PSJ2

Page 1: ...b www incacontrol com au Design Manufacture of Custom built switchboards Electronic control equipment AC DC pumping controls Installation service INCA MODEL PSJ2 PRESSURE CONTROLLER USER MANUAL Inca R...

Page 2: ...igh pressure shutdown 6 4 4 Setting high pressure time delay 6 4 5 Duty start pressure 6 4 6 Duty stop pressure 6 4 7 Standby start pressure 6 4 8 Standby stop pressure 6 4 9 Pressure sensor calibrati...

Page 3: ...ly programmable to suit transducer range Flow Totaliser up to 32000 kilolitres Inputs 2 wire plus shield connected to terminals located on panel base plate for pressure transducer 2 wire plus earth co...

Page 4: ...ntrol panel connect the positive lead to terminal No10 the return signal to terminal No12 The screen must be solidly earthed with a saddle clamp providing the best screening earth Float switch wiring...

Page 5: ...the blue buttons You can only enter a value of as many digits as is displayed on the screen Example an input that displays 3 digits can only have 3 digit entered 3 2 Power Up Display On power up the...

Page 6: ...ss 0 press 0 then press Return Arrow button Press the RIGHT ARROW Button to move onto the next Page 4 4 Setting High Pressure Time Delay High pressure time delay will now be displayed The Cursor will...

Page 7: ...controller The pump will then be controlled via the duty pressure on off settings If selected to OFF the pump will run via the duty pressure on off settings To select the Irrigation control enter 1 i...

Page 8: ...il manually reset If a low level float switch is connected closes this input the pump will be shutdown until the level rises to reset the float switch automatically restart the pump 5 2 Manual Off Aut...

Page 9: ...Fail displayed on screen Reset pump overload by pressing overload reset button on to of overload If problem continues call for service 5 System Produces a Low Pressure shutdown Press the reset button...

Page 10: ...r Time delay before pump shuts down 5sec Duty Pump on Duty Pump start set point 400kPa Duty Pump off Duty Pump stop set point 500kPa Standby Pump on Standby Pump Start set Point 350kpa Standby Pump of...

Page 11: ...tention under guarantee unless otherwise agreed must be returned to the factory freight paid and if accepted for free repair will be returned to the customers address in Australia free of charge Equip...