HX7+ ASD Installation and Operation Manual
operation. This input terminal may be programmed to any of the functions listed in
).
RR
— The default function assigned to this terminal is
Frequency Mode 1
. The
RR
terminal accepts a
0 – 10 VDC input signal that is used to control the function assigned to this terminal. This input terminal
may be programmed to control the speed, torque, or Acc/Dec of the motor via an amplitude setting or
regulate the ASD output by setting a limit. The gain and bias of this terminal may be adjusted for
application-specific suitability (see
–
RX
— The default function assigned to this terminal is
Torque Command
. The
RX
terminal accepts a
±10 VDC input signal that is used to control the function assigned to this terminal. This input terminal
may be programmed to control the speed or torque of the motor via an amplitude setting or regulate the
ASD output by setting a limit. The gain and bias of this terminal may be adjusted for application-
specific suitability (see
Note:
The
VI
terminal or the
II
terminal may be used to control the speed or torque of the
motor, but both cannot be used simultaneously. In cases where either terminal may be
used for a function, they will be listed in the manual as
VI/II
.
VI
— The
VI
terminal is an isolated voltage input that may be used to control the output speed or output
torque of the ASD. Select
VI/II
for speed control or select
VI/II
at
for torque control. The
VI
terminal receives a 0 – 10 VDC input signal that controls the output 0.0 –
Maximum Frequency
speed output or the -250% – 250% torque output. Terminal scaling is accomplished via
.
The gain and bias of this terminal may be adjusted for application-specific suitability (see
and
II
— The
II
terminal is an isolated current input that may be used to control the output speed or output
torque of the ASD. Select
VI/II
for speed control or select
VI/II
for torque control. The
II
terminal receives a 0 – 20 mA input signal that controls the output 0.0 –
Maximum Frequency
speed
output or the -250% – 250% torque output. Terminal scaling is accomplished via
. The gain
and bias of this terminal may be adjusted for application-specific suitability (see
and
).
P24
— +24 VDC at 200 mA power supply for customer use.
PP
— The function of output
PP
is to provide a 10 VDC/10 mADC (max.) output that may be divided
using a potentiometer. The tapped voltage is applied to the
RR
input to provide manual control of the
RR
programmed function.
OUT1
— The default setting for this output terminal is the
Output Low Speed
. This output terminal
may be programmed to provide an indication that any of the events listed in
occurred or are active. This function may be used to signal the operator or to activate external
equipment or a brake (see
). The OUT1 contact is rated at 2 A/120 VAC and 2 A/30 VDC.
OUT2
— The default setting for this output terminal is the
Fault
. This output terminal may be
programmed to provide an indication that any of the events list in
has occurred or
are active. This function may be used to signal the operator or to activate external equipment or a brake
(see
). The OUT1 contact is rated at 2 A/120 VAC and 2 A/30 VDC.
FP
— The default function of this output terminal is to output a series of pulses at a rate that is a
function of the ASD output frequency (50 mA max. at 1.0 kHz to 43.3 kHz). As the output frequency of
the ASD changes so does the
FP
output pulse rate. This terminal may be programmed to provide an
output pulse rate that is proportional to the magnitude of the user-selected item from
. For further information on this terminal, see parameter
AM
—
This output terminal produces an output current that is proportional to the output frequency of
the ASD or of the magnitude of the function assigned to this terminal. The available assignments for
this output terminal are listed in
. For further information on this terminal, see
Summary of Contents for HX7+ ASD
Page 2: ...DN 67017 001 February 2014 HX7 ASD Installation Operation Manual ...
Page 227: ...218 HX7 ASD Installation and Operation Manual Figure 35 200 kVA Sine Wave NEMA 1 Enclosure ...
Page 231: ...222 HX7 ASD Installation and Operation Manual Figure 39 200 kVA Sine Wave NEMA 3R Enclosure ...
Page 235: ...226 HX7 ASD Installation and Operation Manual Figure 43 66 163 kVA 18 Pulse Enclosure ...
Page 236: ...HX7 ASD Installation and Operation Manual 227 Figure 44 200 kVA 18 Pulse Enclosure ...
Page 237: ...228 HX7 ASD Installation and Operation Manual Figure 45 260 518 kVA 18 Pulse Enclosure ...
Page 238: ...HX7 ASD Installation and Operation Manual 229 Figure 46 518 700 kVA 18 Pulse Enclosure ...