192
HX7+ ASD Installation and Operation Manual
124 125
Pre-excite Motor
— Activation applies an excitation current to the motor (holds shaft stationary) for the duration of
the connection.
126 127
System Consistent Sequence
(BC: braking command)
— Not Used.
128 129
System Consistent Sequence
(B: braking release)
— Activation initiates the brake release command. This
setting requires that another discrete input terminal be set to
System Consistent Sequence
(BA: braking answer)] to
complete the brake release command and to convey the status of the braking system to the user or to a dependent
subsystem.
Once the braking release function is initiated, the
Trouble Internal Timer
begins to count down (
Trouble Internal
Timer
). Should the count-down timer expire before the brake releases or before the
Braking
Answer
is returned, fault
E-11
will occur. Otherwise, the brake releases the motor and normal motor operations
resume.
The
Braking Release
function is primarily used at startup; but, may be used when the brake is applied while the motor
is running.
130 131
System Consistent Sequence
(BA: braking answer)
— This setting is required when the
Braking Release
function is used. The function of this input terminal is to receive the returned the status of the braking system. The
returned status is either
Released
or
Not Released
.
If
Released
is returned within the time setting of
, normal system function resumes.
If
Not Released
is returned or if the
time setting times out before either signal is returned, then fault
E-11
occurs.
The returned signal may also be used to notify the user or control a dependent subsystem.
132 133
System Consistent Sequence
(BT: braking test)
— Factory use.
134 135
Output Frequency Hold
— Not Used.
Note:
NO/NC = Normally Open/Normally Closed. NO/NC selection numbers are used when making system changes via
communications.
Table 14.(Continued) Discrete Input Terminal Assignment Selections and Descriptions.
Sel. No.
Terminal Selection Descriptions
NO NC
Summary of Contents for HX7+ ASD
Page 2: ...DN 67017 001 February 2014 HX7 ASD Installation Operation Manual ...
Page 227: ...218 HX7 ASD Installation and Operation Manual Figure 35 200 kVA Sine Wave NEMA 1 Enclosure ...
Page 231: ...222 HX7 ASD Installation and Operation Manual Figure 39 200 kVA Sine Wave NEMA 3R Enclosure ...
Page 235: ...226 HX7 ASD Installation and Operation Manual Figure 43 66 163 kVA 18 Pulse Enclosure ...
Page 236: ...HX7 ASD Installation and Operation Manual 227 Figure 44 200 kVA 18 Pulse Enclosure ...
Page 237: ...228 HX7 ASD Installation and Operation Manual Figure 45 260 518 kVA 18 Pulse Enclosure ...
Page 238: ...HX7 ASD Installation and Operation Manual 229 Figure 46 518 700 kVA 18 Pulse Enclosure ...