170
HX7+ ASD Installation and Operation Manual
Low Current Trip
Program
Protection
Low Current
This parameter
Enables/Disables
the low-current trip feature.
When enabled, the drive will trip on a low-current fault if the output current of
the drive falls below the level defined at
and remains there for the time set
Settings:
0 — Disabled
1 — Enabled (box checked)
Direct Access Number — F610
Parameter Type —
Check Box
Factory Default —
Disabled
Changeable During Run —
No
Low Current Trip Threshold
Program
Protection
Low Current
When the low-current monitor is enabled, this function sets the low-current trip
threshold. The threshold value is entered as a percentage of the maximum rating
of the drive.
Direct Access Number — F611
Parameter Type —
Numerical
Factory Default —
0.00
Changeable During Run —
Yes
Minimum — 0.00
Maximum — 100.0
Units — %
Low Current Trip Threshold Time
Program
Protection
Low Current
When the low-current monitor is enabled, this function sets the time that the
low-current condition must exist to cause a trip.
Direct Access Number — F612
Parameter Type —
Numerical
Factory Default —
0
Changeable During Run —
Yes
Minimum — 0
Maximum — 255
Units — Seconds
Short Circuit Test
Program
Protection
Arm Short Check
This parameter determines when the system will perform an
Output Short
Circuit
test.
Settings:
0 — Every Run
1 — Every Powerup
2 — Never
Direct Access Number — F613
Parameter Type —
Selection List
Factory Default —
Every Run
Changeable During Run —
No
Short Circuit Test Duration
Program
Protection
Arm Short Check
This parameter sets the pulse width of the ASD output pulse that is applied to
the motor during an
Output Short Circuit
test.
Direct Access Number — F614
Parameter Type —
Numerical
Factory Default — (ASD dependent)
Changeable During Run —
No
Minimum — 1
Maximum — 100
Units — µS
Summary of Contents for HX7+ ASD
Page 2: ...DN 67017 001 February 2014 HX7 ASD Installation Operation Manual ...
Page 227: ...218 HX7 ASD Installation and Operation Manual Figure 35 200 kVA Sine Wave NEMA 1 Enclosure ...
Page 231: ...222 HX7 ASD Installation and Operation Manual Figure 39 200 kVA Sine Wave NEMA 3R Enclosure ...
Page 235: ...226 HX7 ASD Installation and Operation Manual Figure 43 66 163 kVA 18 Pulse Enclosure ...
Page 236: ...HX7 ASD Installation and Operation Manual 227 Figure 44 200 kVA 18 Pulse Enclosure ...
Page 237: ...228 HX7 ASD Installation and Operation Manual Figure 45 260 518 kVA 18 Pulse Enclosure ...
Page 238: ...HX7 ASD Installation and Operation Manual 229 Figure 46 518 700 kVA 18 Pulse Enclosure ...