HX7+ ASD Installation and Operation Manual
103
VI/II Torque Reference Setpoint #2
Program
Torque Setting
Setpoints
VI/II
This parameter is used to set the gain and bias of the
VI/II
input terminal when
the
VI/II
terminal is used as the control input while operating in the
Torque
Control
mode.
This is accomplished by establishing an associated
V/f
output pattern for a
given
VI/II
input level.
See
VI/II Speed Reference #1
for further information on this setting.
This parameter sets
VI/II
Torque Reference Setpoint #2
and is the output
torque value that is associated with setting of
VI/II Speed Reference #2
while
operating in the
Torque
control mode.
Direct Access Number — F206
Parameter Type —
Numerical
Factory Default —
100.00
Changeable During Run —
Yes
Minimum — 0.00
Maximum — 250.0
Units — %
Frequency Mode #2
Program
Fundamentals
Standard Mode Selection
This parameter selects the source of the frequency command signal to be used
as
Frequency Mode #2
in the event that
Frequency Mode #1
is disabled or if
Frequency Mode #2
is set up as the primary control parameter. See
and
for additional information on this setting.
Settings:
1 — Use VI/II
2 — Use RR
3 — Use RX
4 — Use Option Card RX2
5 — Use CN8 Option (LED Keypad)
6 — Use Binary/BCD Input
7 — Use Common Serial (TTL)
8 — Use RS232/RS485
9 — Use Communication Card
10 — Use Motorized Pot. Simulation
11 — Use Pulse Input Option
Direct Access Number — F207
Parameter Type —
Selection List
Factory Default —
VI/II
Changeable During Run —
Yes
Mode #1/#2 Switching Frequency
Program
Fundamentals
Standard Mode Selection
Mode #1/#2
Switching Frequency
This parameter sets the threshold frequency that will be used in
determine if
Frequency Source #1
or
#2
will control the output of the ASD.
See
or additional information on this setting.
Direct Access Number — F208
Parameter Type —
Numerical
Factory Default —
1.0
Changeable During Run —
Yes
Minimum — 0.1
Maximum —
Max. Freq.
Units — Hz
Summary of Contents for HX7+ ASD
Page 2: ...DN 67017 001 February 2014 HX7 ASD Installation Operation Manual ...
Page 227: ...218 HX7 ASD Installation and Operation Manual Figure 35 200 kVA Sine Wave NEMA 1 Enclosure ...
Page 231: ...222 HX7 ASD Installation and Operation Manual Figure 39 200 kVA Sine Wave NEMA 3R Enclosure ...
Page 235: ...226 HX7 ASD Installation and Operation Manual Figure 43 66 163 kVA 18 Pulse Enclosure ...
Page 236: ...HX7 ASD Installation and Operation Manual 227 Figure 44 200 kVA 18 Pulse Enclosure ...
Page 237: ...228 HX7 ASD Installation and Operation Manual Figure 45 260 518 kVA 18 Pulse Enclosure ...
Page 238: ...HX7 ASD Installation and Operation Manual 229 Figure 46 518 700 kVA 18 Pulse Enclosure ...