S1 – S4 Input Terminal Delay
Program
Terminal Selection
In Terminal Delays
This parameter delays the response of the drive to any change in the
S1 – S4
terminal input by the programmed value (see waveforms at
).
The delay may be increased to provide additional electrical noise immunity or
to prevent the ASD from responding to contact bounce or chatter.
Direct Access Number — F144
Parameter Type —
Numerical
Factory Default —
8.0
Changeable During Run —
No
Minimum — 2.0
Maximum — 200.0
Units — mS
S5 – S16 Input Terminal Delay
Program
Terminal Selection
In Terminal Delays
This parameter delays the response of the drive to any change in the
S5 – S16
terminal input by the programmed value (see waveforms at
).
The delay may be increased to provide additional electrical noise immunity or
to prevent the ASD from responding to contact bounce or chatter.
Direct Access Number — F145
Parameter Type —
Numerical
Factory Default —
8.0
Changeable During Run —
No
Minimum — 2.0
Maximum — 200.0
Units — mS
OUT1 On Delay
Program
Terminal Selection
Out Terminal Delays
Once the condition is met to close the
OUT1
(
A
&
C
) output terminals, this
parameter delays the closing of the terminals by the programmed value.
For example, if
the
OUT1
function is programmed as
Over-Torque Alarm
,
OUT1
will close 2.0 mS (the default value for
OUT1 On Delay
) after the over-
torque condition occurs.
The delay may be increased to prevent relay chatter.
Direct Access Number — F150
Parameter Type —
Numerical
Factory Default —
2.0
Changeable During Run —
No
Minimum — 2.0
Maximum — 200.0
Units — mS
OUT2 On Delay
Program
Terminal Selection
Out Terminal Delays
This parameter delays the closing of the
OUT2
(
A
&
C
) output terminals by the
programmed value (see waveforms at
The delay may be increased to prevent relay chatter.
Direct Access Number — F151
Parameter Type —
Numerical
Factory Default —
2.0
Changeable During Run —
No
Minimum — 2.0
Maximum — 200.0
Units — mS
Summary of Contents for HX7+ ASD
Page 2: ...DN 67017 001 February 2014 HX7 ASD Installation Operation Manual ...
Page 227: ...218 HX7 ASD Installation and Operation Manual Figure 35 200 kVA Sine Wave NEMA 1 Enclosure ...
Page 231: ...222 HX7 ASD Installation and Operation Manual Figure 39 200 kVA Sine Wave NEMA 3R Enclosure ...
Page 235: ...226 HX7 ASD Installation and Operation Manual Figure 43 66 163 kVA 18 Pulse Enclosure ...
Page 236: ...HX7 ASD Installation and Operation Manual 227 Figure 44 200 kVA 18 Pulse Enclosure ...
Page 237: ...228 HX7 ASD Installation and Operation Manual Figure 45 260 518 kVA 18 Pulse Enclosure ...
Page 238: ...HX7 ASD Installation and Operation Manual 229 Figure 46 518 700 kVA 18 Pulse Enclosure ...