HX7+ ASD Installation and Operation Manual
175
Earth Fault Trip Level
Program
Special Control
Earth Fault
This parameter sets the threshold level (%) that must be exceeded to meet the
Earth Fault Trip
activation criteria.
Direct Access Number — F642
Parameter Type —
Numerical
Factory Default —
100
Changeable During Run —
Yes
Minimum — 0.00
Maximum — 100
Units — %
Earth Fault Trip Time
Program
Special Control
Earth Fault
In the event that the
Earth Fault Trip
activation criteria is met, a timer begins
to count down to zero. Upon reaching zero, the
Earth Fault Trip
is activated.
This parameter sets the start-time of the count-down timer.
Direct Access Number — F643
Parameter Type —
Numerical
Factory Default —
1.00
Changeable During Run —
Yes
Minimum — 0.00
Maximum — 2.50
Units — Seconds
Acc/Dec Base Frequency Adjustment
Program
Terminal Selection
Analog In Functions
This parameter
Enables/Disables
the feature that allows for the external
adjustment of the
Base Frequency
. When enabled, either
VI/II
or
RR
may be
used as an input source for the modification of the
Base Frequency
setting.
Settings:
0 — Disabled
1 — VI/II
2 — RR
Direct Access Number — F650
Parameter Type —
Selection List
Factory Default —
Disabled
Changeable During Run —
Yes
Upper Limit Frequency Adjustment
Program
Terminal Selection
Analog In Functions
This parameter
Enables/Disables
the feature that allows for the external
adjustment of the
Upper Limit
. When enabled, either
VI/II
or
RR
may be used
as an input source for the modification of the
Upper Limit
setting.
Settings:
0 — Disabled
1 — VI/II
2 — RR
Direct Access Number — F651
Parameter Type —
Selection List
Factory Default —
Disabled
Changeable During Run —
Yes
Summary of Contents for HX7+ ASD
Page 2: ...DN 67017 001 February 2014 HX7 ASD Installation Operation Manual ...
Page 227: ...218 HX7 ASD Installation and Operation Manual Figure 35 200 kVA Sine Wave NEMA 1 Enclosure ...
Page 231: ...222 HX7 ASD Installation and Operation Manual Figure 39 200 kVA Sine Wave NEMA 3R Enclosure ...
Page 235: ...226 HX7 ASD Installation and Operation Manual Figure 43 66 163 kVA 18 Pulse Enclosure ...
Page 236: ...HX7 ASD Installation and Operation Manual 227 Figure 44 200 kVA 18 Pulse Enclosure ...
Page 237: ...228 HX7 ASD Installation and Operation Manual Figure 45 260 518 kVA 18 Pulse Enclosure ...
Page 238: ...HX7 ASD Installation and Operation Manual 229 Figure 46 518 700 kVA 18 Pulse Enclosure ...