HX7+ ASD Installation and Operation Manual
11
CE Compliance Requirements
In Europe, the
and
requires that the CE mark be placed on the
product as an indication of compliance to these directives.
The ASD is designed to be installed in an enclosure and is used in conjunction with other machines or
systems. Because the ASD does not function alone, it is not subject to the EMC Directive.
However, because the ASD is subjected to the Low-Voltage Directive, the CE mark must be placed on
all ASDs.
The CE mark must be placed on all machines and systems with a built-in ASD because the machines
and systems are subject to the above directives.
If the ASD is the final product, it may also be subject to machine-related directives. When required, it is
the responsibility of Toshiba International Corporation to place the CE mark on qualifying ASDs.
The CE Compliance section provides installation information and other required measures to satisfy the
EMC Directive and the Low-Voltage Directive.
Toshiba International Corporation has tested representative ASD models that were installed as
described in this manual to ensure compliance with the EMC Directive. Because system compliance is a
function of the installation and connectivity, not all ASDs can be tested for EMC Directive compliance.
Applicable EMC standards vary depending on the composition of the enclosure in which the ASD is
installed, the relationship with other electrical devices installed in the enclosure, wiring conditions,
equipment layout, etc. To that end, ensure that your machine or system complies with the EMC
standards as a whole.
Toshiba International Corporation has applied the following standards for systems deployed in the
European market.
Table 1. European Market Standards.
Category
Subcategory
Product Standards
Test Standard and Level
Emission
Radiated
EN 61800-3
EN55011 Class A Group 1
Conducted
EN55011 Class A Group 1
Immunity
Generic Industrial
EN 61000-6-2
Electrostatic Discharge
EN 61000-4-2
Radiated
EN 61000-4-3
Electrical Fast Transient Burst
EN 61000-4-4
Lightning Surge
EN 61000-4-5
Conducted
EN 61000-4-6
Voltage Dip
EN 61000-4-11
Generic Standards
EN 61000-6-4
Adjustable Speed Electronic Power Drive Systems
EN 61800-5-1
Summary of Contents for HX7+ ASD
Page 2: ...DN 67017 001 February 2014 HX7 ASD Installation Operation Manual ...
Page 227: ...218 HX7 ASD Installation and Operation Manual Figure 35 200 kVA Sine Wave NEMA 1 Enclosure ...
Page 231: ...222 HX7 ASD Installation and Operation Manual Figure 39 200 kVA Sine Wave NEMA 3R Enclosure ...
Page 235: ...226 HX7 ASD Installation and Operation Manual Figure 43 66 163 kVA 18 Pulse Enclosure ...
Page 236: ...HX7 ASD Installation and Operation Manual 227 Figure 44 200 kVA 18 Pulse Enclosure ...
Page 237: ...228 HX7 ASD Installation and Operation Manual Figure 45 260 518 kVA 18 Pulse Enclosure ...
Page 238: ...HX7 ASD Installation and Operation Manual 229 Figure 46 518 700 kVA 18 Pulse Enclosure ...