Forward Speed Limit Input
Program
Torque Setting
Torque Speed Limit
This parameter
Enables/Disables
the
Forward Speed Limit Input
control
function. When enabled and operating in the
Torque Control
mode, the
forward speed limit is controlled by the terminal selected here. If
Setting
is
Forward Speed Limit
input.
Settings:
0 — Disabled
1 — VI/II
2 — RR
3 — RX
4 — RX2 (option)
5 — Setting (of
Direct Access Number — F425
Parameter Type —
Selection List
Factory Default —
Disabled
Changeable During Run —
Yes
Forward Speed Limit Level
Program
Torque Setting
Torque Control
This parameter provides a value to be used as the
Forward Speed Limit
setting
if
Setting
is selected at
.
Direct Access Number — F426
Parameter Type —
Numerical
Factory Default —
80.0
Changeable During Run —
Yes
Minimum — 0.00
Maximum —
Upper Limit
Units — Hz
Reverse Speed Limit Input
Program
Torque Setting
Torque Control
This parameter
Enables/Disables
the
Reverse Speed Limit Input
control
function. When enabled and operating in the
Torque Control
mode, the reverse
speed limit is controlled by the terminal selected here. If
Setting
is selected, the
value set at
is used as the
Reverse Speed Limit
input.
Settings:
0 — Disabled
1 — VI/II
2 — RR
3 — RX
4 — RX2 (option)
5 — Setting (of
Direct Access Number — F427
Parameter Type —
Selection List
Factory Default —
Disabled
Changeable During Run —
Yes
Reverse Speed Limit Level
Program
Torque Setting
Torque Control
This parameter provides a value to be used as the
Reverse Speed Limit
setting
if
Setting
is selected at
.
Direct Access Number — F428
Parameter Type —
Numerical
Factory Default —
80.0
Changeable During Run —
Yes
Minimum — 0.00
Maximum —
Upper Limit
Units — Hz
Summary of Contents for HX7+ ASD
Page 2: ...DN 67017 001 February 2014 HX7 ASD Installation Operation Manual ...
Page 227: ...218 HX7 ASD Installation and Operation Manual Figure 35 200 kVA Sine Wave NEMA 1 Enclosure ...
Page 231: ...222 HX7 ASD Installation and Operation Manual Figure 39 200 kVA Sine Wave NEMA 3R Enclosure ...
Page 235: ...226 HX7 ASD Installation and Operation Manual Figure 43 66 163 kVA 18 Pulse Enclosure ...
Page 236: ...HX7 ASD Installation and Operation Manual 227 Figure 44 200 kVA 18 Pulse Enclosure ...
Page 237: ...228 HX7 ASD Installation and Operation Manual Figure 45 260 518 kVA 18 Pulse Enclosure ...
Page 238: ...HX7 ASD Installation and Operation Manual 229 Figure 46 518 700 kVA 18 Pulse Enclosure ...