HX7+ ASD Installation and Operation Manual
RX Torque Reference Setpoint #2
Program
Torque Setting
Setpoints
RX
This parameter is used to set the gain and bias of the
RX
input terminal when
the
RX
terminal is used as the control input while operating in the
Torque
Control
mode.
This is accomplished by establishing an associated
V/f
output pattern for a
given
RX
input level.
See
RX Speed Reference #1
for further information on this setting.
This parameter sets
RX
Torque Reference Setpoint #2
and is the output torque
value that is associated with setting of
RX Speed Reference #2
while operating
in the
Torque
control mode.
Direct Access Number — F221
Parameter Type —
Numerical
Factory Default —
100.00
Changeable During Run —
Yes
Minimum — -250.00
Maximum — 250.00