HX7+ ASD Installation and Operation Manual
Regeneration Torque Limit #2
Program
Torque Setting
Manual Torque Limit
This parameter is used to set the negative torque upper limit for the #2 motor
profile when multiple motors are controlled by a single drive or when a single
motor is to be controlled by multiple profiles.
Direct Access Number — F445
Parameter Type —
Numerical
Factory Default —
250.0
Changeable During Run —
Yes
Minimum — 0.00
Maximum — 250.0
Units — %
Driving Torque Limit #3
Program
Torque Setting
Manual Torque Limit
This parameter is used to set the positive torque upper limit for the #3 motor
profile when multiple motors are controlled by a single drive or when a single
motor is to be controlled by multiple profiles.
Direct Access Number — F446
Parameter Type —
Numerical
Factory Default —
250.0
Changeable During Run —
Yes
Minimum — 0.00
Maximum — 250.0
Units — %
Regeneration Torque Limit #3
Program
Torque Setting
Manual Torque Limit
This parameter is used to set the negative torque upper limit for the #3 motor
profile when multiple motors are controlled by a single drive or when a single
motor is to be controlled by multiple profiles.
Direct Access Number — F447
Parameter Type —
Numerical
Factory Default —
250.0
Changeable During Run —
Yes
Minimum — 0.00
Maximum — 250.0
Units — %
Driving Torque Limit #4
Program
Torque Setting
Manual Torque Limit
This parameter is used to set the positive torque upper limit for the #4 motor
profile when multiple motors are controlled by a single drive or when a single
motor is to be controlled by multiple profiles.
Direct Access Number — F448
Parameter Type —
Numerical
Factory Default —
250.0
Changeable During Run —
Yes
Minimum — 0.00
Maximum — 250.0
Units — %
Regeneration Torque Limit #4
Program
Torque Setting
Manual Torque Limit
This parameter is used to set the negative torque upper limit for the #4 motor
profile when multiple motors are controlled by a single drive or when a single
motor is to be controlled by multiple profiles.
Direct Access Number — F449
Parameter Type —
Numerical
Factory Default —
250.0
Changeable During Run —
Yes
Minimum — 0.00
Maximum — 250.0
Units — %
Torque Limit Mode
Program
Torque Setting
Torque Limit Settings
Contact the
Toshiba Customer Support Center
for information on this
parameter.
Settings:
0 — Driving/Regen
1 — Positive/Negative
Direct Access Number — F450
Parameter Type —
Selection List
Factory Default —
Driving/Regen
Changeable During Run —
No
Summary of Contents for HX7+ ASD
Page 2: ...DN 67017 001 February 2014 HX7 ASD Installation Operation Manual ...
Page 227: ...218 HX7 ASD Installation and Operation Manual Figure 35 200 kVA Sine Wave NEMA 1 Enclosure ...
Page 231: ...222 HX7 ASD Installation and Operation Manual Figure 39 200 kVA Sine Wave NEMA 3R Enclosure ...
Page 235: ...226 HX7 ASD Installation and Operation Manual Figure 43 66 163 kVA 18 Pulse Enclosure ...
Page 236: ...HX7 ASD Installation and Operation Manual 227 Figure 44 200 kVA 18 Pulse Enclosure ...
Page 237: ...228 HX7 ASD Installation and Operation Manual Figure 45 260 518 kVA 18 Pulse Enclosure ...
Page 238: ...HX7 ASD Installation and Operation Manual 229 Figure 46 518 700 kVA 18 Pulse Enclosure ...