HX7+ ASD Installation and Operation Manual
171
Over-Torque Trip
Program
Protection
Over Torque
This parameter
Enables/Disables
the
Over-Torque Tripping
function.
When enabled, the ASD trips if an output torque value greater than the setting
of
exists for a time longer than the setting of
.
When disabled, the ASD does not trip due to an over-torque condition.
Settings:
0 — Disabled
1 — Enabled (box checked)
Direct Access Number — F615
Parameter Type —
Check Box
Factory Default —
Disabled
Changeable During Run —
No
Over-Torque Trip/Alarm Level (Positive Torque)
Program
Protection
Over Torque
This parameter sets the torque threshold level that is used as a setpoint for over-
torque tripping. This setting is a percentage of the maximum rated torque of the
drive.
Direct Access Number — F616
Parameter Type —
Numerical
Factory Default —
150.0
Changeable During Run —
No
Minimum — 0.00
Maximum — 250.0
Units — %
Over-Torque Trip/Alarm Level (Negative Torque)
Program
Protection
Over Torque
This parameter sets the torque threshold level that is used as a setpoint for over-
torque tripping during regeneration. This setting is a percentage of the
maximum rated torque of the drive.
Direct Access Number — F617
Parameter Type —
Numerical
Factory Default —
150.0
Changeable During Run —
No
Minimum — 0.00
Maximum — 250.0
Units — %
Over-Torque Detection Time
Program
Protection
Over Torque
This parameter sets the amount of time that the over-torque condition may
exceed the tripping threshold level set at
and
before a trip occurs.
Direct Access Number — F618
Parameter Type —
Numerical
Factory Default —
0.50
Changeable During Run —
No
Minimum — 0.00
Maximum — 100.0
Units — Seconds
Cooling Fan Control
Program
Protection
Cooling Fan
This parameter sets the cooling fan run-time command.
Settings:
0 — Automatic
1 — Always On
2 — Internal and External Temp Controlled
3 — Internal-Auto/External-Temp Controlled
4 — Internal-Temp Controlled/External-Auto
Direct Access Number — F620
Parameter Type —
Selection List
Factory Default —
Automatic
Changeable During Run —
Yes
Summary of Contents for HX7+ ASD
Page 2: ...DN 67017 001 February 2014 HX7 ASD Installation Operation Manual ...
Page 227: ...218 HX7 ASD Installation and Operation Manual Figure 35 200 kVA Sine Wave NEMA 1 Enclosure ...
Page 231: ...222 HX7 ASD Installation and Operation Manual Figure 39 200 kVA Sine Wave NEMA 3R Enclosure ...
Page 235: ...226 HX7 ASD Installation and Operation Manual Figure 43 66 163 kVA 18 Pulse Enclosure ...
Page 236: ...HX7 ASD Installation and Operation Manual 227 Figure 44 200 kVA 18 Pulse Enclosure ...
Page 237: ...228 HX7 ASD Installation and Operation Manual Figure 45 260 518 kVA 18 Pulse Enclosure ...
Page 238: ...HX7 ASD Installation and Operation Manual 229 Figure 46 518 700 kVA 18 Pulse Enclosure ...