HX7+ ASD Installation and Operation Manual
117
PG Speed Frequency #1
Program
Frequency Setting
Speed Reference Setpoints
PG
This parameter is used to set the gain and bias of the
PG
input terminal when a
shaft-mounted encoder is used as the feedback transducer while operating in the
Speed Control
mode.
See
PG Speed Reference #1
(
) for further information on this setting.
This parameter sets
PG Speed Frequency #1
and is the frequency that is
associated with the setting of
PG Speed Reference #1
while operating in the
Speed Control
mode.
Direct Access Number — F235
Parameter Type —
Numerical
Factory Default —
0.00
Changeable During Run —
Yes
Minimum — -
Max. Freq.
(
Maximum —
Max. Freq.
Units — Hz
PG Speed Reference #2
Program
Frequency Setting
Speed Reference Setpoints
PG
This parameter is used to set the gain and bias of the
PG
input terminal when a
shaft-mounted encoder is used as the feedback transducer while operating in the
Speed Control
mode.
See
PG Speed Reference #1
for further information on this setting when used
for
Speed
control.
This parameter sets the
PG
input level that is associated with
PG Speed
Frequency #2
while operating in the
Speed
control mode.
Direct Access Number — F236
Parameter Type —
Numerical
Factory Default —
100.00
Changeable During Run —
Yes
Minimum — -100.0
Maximum — 100.0
Units — %
PG Speed Frequency #2
Program
Frequency Setting
Speed Reference Setpoints
PG
This parameter is used to set the gain and bias of the
PG
input terminal when a
shaft-mounted encoder is used as the feedback transducer while operating in the
Speed Control
mode.
See
PG Speed Reference #1
for further information on this setting when used
for
Speed
control.
This parameter sets
PG Speed Frequency #2
and is the frequency that is
associated with the setting of
PG Speed Reference #2
while operating in the
Speed Control
mode.
Direct Access Number — F237
Parameter Type —
Numerical
Factory Default —
80.00
Changeable During Run —
Yes
Minimum — -
Max. Freq.
(
Maximum —
Max. Freq.
Units — Hz
Startup Frequency
Program
Special Control
Frequency Control
The output of the drive will remain at 0.0 Hz until the programmed speed value
exceeds this setting during startup. Once exceeded during startup, the output
frequency of the drive will accelerate to the programmed setting.
Output frequencies below the
Startup Frequency
will not be output from the
drive during startup. However, once reaching the
Startup Frequency
, speed
values below the
Startup Frequency
may be output from the drive.
Direct Access Number — F240
Parameter Type —
Numerical
Factory Default —
0.10
Changeable During Run —
Yes
Minimum — 0.0
Maximum — 10.0
Units — Hz
Summary of Contents for HX7+ ASD
Page 2: ...DN 67017 001 February 2014 HX7 ASD Installation Operation Manual ...
Page 227: ...218 HX7 ASD Installation and Operation Manual Figure 35 200 kVA Sine Wave NEMA 1 Enclosure ...
Page 231: ...222 HX7 ASD Installation and Operation Manual Figure 39 200 kVA Sine Wave NEMA 3R Enclosure ...
Page 235: ...226 HX7 ASD Installation and Operation Manual Figure 43 66 163 kVA 18 Pulse Enclosure ...
Page 236: ...HX7 ASD Installation and Operation Manual 227 Figure 44 200 kVA 18 Pulse Enclosure ...
Page 237: ...228 HX7 ASD Installation and Operation Manual Figure 45 260 518 kVA 18 Pulse Enclosure ...
Page 238: ...HX7 ASD Installation and Operation Manual 229 Figure 46 518 700 kVA 18 Pulse Enclosure ...