HX7+ ASD Installation and Operation Manual
137
Position Loop Gain
Program
Feedback Parameters
PG Settings
This parameter provides a divisor for the pulse input when operating in the
Pulse Control
mode.
Direct Access Number — F371
Parameter Type —
Numerical
Factory Default —
4.00
Changeable During Run —
Yes
Minimum — 0.0
Maximum — 100.0
Position Completion Range
Program
Feedback Parameters
PG Settings
During a deceleration ramp, this parameter sets a speed range that must be
attained before the
Stop
command may be executed.
Direct Access Number — F372
Parameter Type —
Numerical
Factory Default —
100
Changeable During Run —
Yes
Minimum — 1
Maximum — 4000
Frequency Limit at Position
Program
Feedback Parameters
PG Settings
While operating in the
Position-Control
mode and using
PG
feedback, this
setting determines the maximum acceleration rate in Hz/second.
Direct Access Number — F373
Parameter Type —
Numerical
Factory Default —
800
Changeable During Run —
Yes
Minimum — 1
Maximum — 8001
Units — Hz/Second
Current Control Proportional Gain
Program
Feedback Parameters
PG Settings
This parameter sets the sensitivity of the drive when monitoring the output
current to control speed. The larger the value entered here, the more sensitive
the drive is to changes in the received feedback.
Direct Access Number — F374
Parameter Type —
Numerical
Factory Default — (ASD dependent)
Changeable During Run —
No
Minimum — 100.0
Maximum — 1000
Current Control Integral Gain
Program
Feedback Parameters
PG Settings
This parameter sets the degree and rate at which the output frequency will be
allowed to change when prompted by changes in the output current.
The larger the value entered here, the quicker/more the drive responds to
changes in feedback.
Direct Access Number — F375
Parameter Type —
Numerical
Factory Default — (ASD dependent)
Changeable During Run —
No
Minimum — 100.0
Maximum — 1250
Summary of Contents for HX7+ ASD
Page 2: ...DN 67017 001 February 2014 HX7 ASD Installation Operation Manual ...
Page 227: ...218 HX7 ASD Installation and Operation Manual Figure 35 200 kVA Sine Wave NEMA 1 Enclosure ...
Page 231: ...222 HX7 ASD Installation and Operation Manual Figure 39 200 kVA Sine Wave NEMA 3R Enclosure ...
Page 235: ...226 HX7 ASD Installation and Operation Manual Figure 43 66 163 kVA 18 Pulse Enclosure ...
Page 236: ...HX7 ASD Installation and Operation Manual 227 Figure 44 200 kVA 18 Pulse Enclosure ...
Page 237: ...228 HX7 ASD Installation and Operation Manual Figure 45 260 518 kVA 18 Pulse Enclosure ...
Page 238: ...HX7 ASD Installation and Operation Manual 229 Figure 46 518 700 kVA 18 Pulse Enclosure ...