HX7+ ASD Installation and Operation Manual
181
Stop Pattern
No path available (Direct Access Only)
While operating using the
CN8 Option
(LED Keypad)
the
Stop Pattern
parameter determines the method used to stop the motor when the stop
command is issued via a
Stop
command from the
CN8 Option
.
The
Decel Stop
setting enables the
Dynamic Braking
system that is setup at
or the
DC Injection Braking
system that is setup at
, and
The
Coast Stop
setting allows the motor to stop at the rate allowed by the
inertia of the load.
Settings:
0 — Decel Stop
1 — Coast Stop
Note:
The
Stop Pattern
setting has no effect on the
Emergency Off
settings of
. Press
ESC
from the
screen to access this parameter.
Direct Access Number — F721
Parameter Type —
Selection List
Factory Default —
Decel Stop
Changeable During Run —
Yes
Torque Limit Group
No path available (Direct Access Only)
While operating using the
CN8 Option
(LED Keypad)
this parameter is
used to select 1 of 4 preset positive torque limits to apply to the active motor.
The settings of profiles 1 – 4 may be setup at
,
respectively.
Settings:
1 — Group 1
2 — Group 2
3 — Group 3
4 — Group 4
Note:
Press
ESC
from the
screen to access this
parameter.
Direct Access Number — F723
Parameter Type —
Selection List
Factory Default —
1
Changeable During Run —
Yes
Feedback in Panel Mode
No path available (Direct Access Only)
While operating using the
CN8 Option
(LED Keypad)
this parameter
Enables/Disables
PID
feedback control.
Settings:
0 — Enabled
1 — Disabled
Note:
Press
ESC
from the
screen to access this
parameter.
Direct Access Number — F724
Parameter Type —
Selection List
Factory Default —
Enabled
Changeable During Run —
Yes
CN8 Option (LED Keypad) Override Multiplication Gain
Program
Feedback Parameters
Override Control
If operating using the
CN8 Option
(LED Keypad)
this parameter provides a
value to be used in the event that
Setting
is selected for the
Frequency
Override Multiplying Input
).
Direct Access Number — F729
Parameter Type —
Numerical
Factory Default —
0.00
Changeable During Run —
Yes
Minimum — -100.00
Maximum — 100.00
Summary of Contents for HX7+ ASD
Page 2: ...DN 67017 001 February 2014 HX7 ASD Installation Operation Manual ...
Page 227: ...218 HX7 ASD Installation and Operation Manual Figure 35 200 kVA Sine Wave NEMA 1 Enclosure ...
Page 231: ...222 HX7 ASD Installation and Operation Manual Figure 39 200 kVA Sine Wave NEMA 3R Enclosure ...
Page 235: ...226 HX7 ASD Installation and Operation Manual Figure 43 66 163 kVA 18 Pulse Enclosure ...
Page 236: ...HX7 ASD Installation and Operation Manual 227 Figure 44 200 kVA 18 Pulse Enclosure ...
Page 237: ...228 HX7 ASD Installation and Operation Manual Figure 45 260 518 kVA 18 Pulse Enclosure ...
Page 238: ...HX7 ASD Installation and Operation Manual 229 Figure 46 518 700 kVA 18 Pulse Enclosure ...