152
HX7+ ASD Installation and Operation Manual
Current Vector Control
Program
Special Control
Special Parameters
This parameter establishes the control margin of modulation when operating in
the
Current Vector Control
mode.
Direct Access Number — F482
Parameter Type —
Numerical
Factory Default —
90.0
Changeable During Run —
Yes
Minimum — 80.0
Maximum — 300.0
Units — %
Voltage Vector Control
Program
Special Control
Special Parameters
This parameter establishes the control margin of modulation while operating in
the
Voltage Vector Control
mode.
Direct Access Number — F483
Parameter Type —
Numerical
Factory Default —
105.0
Changeable During Run —
Yes
Minimum — 80.0
Maximum — 300.0
Units — %
Constant Vector Control
Program
Special Control
Special Parameters
This parameter establishes the control margin of modulation while operating in
the
Constant Vector Control
mode.
Direct Access Number — F484
Parameter Type —
Numerical
Factory Default —
105.0
Changeable During Run —
Yes
Minimum — 80.0
Maximum — 300.0
Units — %
Stall Cooperation Gain at Field Weakening Zone
Program
Special Control
Special Parameters
This parameter determines the degree that the
Stall
function is effective while
operating the motor in the field weakening zone.
Direct Access Number — F485
Parameter Type —
Numerical
Factory Default —
128
Changeable During Run —
Yes
Minimum — 0
Maximum — 255
Excitation Starting Rate
Program
Special Control
Special Parameters
This parameter establishes the rate of increase in the excitation current from a
zero output of the ASD.
Direct Access Number — F486
Parameter Type —
Numerical
Factory Default —
163.8
Changeable During Run —
Yes
Minimum — 1.64
Maximum — 327.6
Compensation Coefficient for Iron Loss
Program
Special Control
Special Parameters
This parameter compensates for losses in the rotor-to-stator coupling of the
excitation and torque current energy.
Direct Access Number — F487
Parameter Type —
Numerical
Factory Default —
105.0
Changeable During Run —
Yes
Minimum — 0
Maximum — 255
Summary of Contents for HX7+ ASD
Page 2: ...DN 67017 001 February 2014 HX7 ASD Installation Operation Manual ...
Page 227: ...218 HX7 ASD Installation and Operation Manual Figure 35 200 kVA Sine Wave NEMA 1 Enclosure ...
Page 231: ...222 HX7 ASD Installation and Operation Manual Figure 39 200 kVA Sine Wave NEMA 3R Enclosure ...
Page 235: ...226 HX7 ASD Installation and Operation Manual Figure 43 66 163 kVA 18 Pulse Enclosure ...
Page 236: ...HX7 ASD Installation and Operation Manual 227 Figure 44 200 kVA 18 Pulse Enclosure ...
Page 237: ...228 HX7 ASD Installation and Operation Manual Figure 45 260 518 kVA 18 Pulse Enclosure ...
Page 238: ...HX7 ASD Installation and Operation Manual 229 Figure 46 518 700 kVA 18 Pulse Enclosure ...