194
HX7+ ASD Installation and Operation Manual
Table 16. Discrete Output Terminal Assignment Selections.
Function
Function
0
Lower Limit (LL)
31
Ready for Operation (including
ST
and
RUN
)
1
Upper Limit (UL)
32
Ready for Operation
2
Low (speed specified at
33
POFF Alarm (poor control power supply)
3
RCH (Acc/Dec completion)
34
System Consistent Sequence (BR: brake release)
4
RCH (speed specified at
35
Alarm Active
5
Fault FL (all)
36
Forward Speed Limit (torque control)
6
Fault FL (except EF or OCL)
37
Reverse Speed Limit (torque control)
7
Over-Current Alarm
38
ASD Healthy Output
8
ASD Overload Alarm
39
Abnormal Communication Alarm 2 (internal cause)
9
Motor Alarm
40
Error Code Output 1 (6-bit error output)
10
Over-Heat Alarm
41
Error Code Output 2 (6-bit error output)
11
Over-Voltage Alarm
42
Error Code Output 3 (6-bit error output)
12
DC Voltage Low Alarm
43
Error Code Output 4 (6-bit error output)
13
Low-current Alarm
44
Error Code Output 5 (6-bit error output)
14
Over-Torque Alarm
45
Error Code Output 6 (6-bit error output)
15
Braking Resistor Overload Alarm
46
Designated Data Output 1 (7-bit transmission output)
16
Emergency Off Active
47
Designated Data Output 2 (7-bit transmission output)
17
Retry Active
48
Designated Data Output 3 (7-bit transmission output)
18
Pattern Operation Switching Output
49
Designated Data Output 4 (7-bit transmission output)
19
PID Deviation Limit
50
Designated Data Output 5 (7-bit transmission output)
20
Start/Stop
51
Designated Data Output 6 (7-bit transmission output)
21
Serious Fault (OCA, OCL, EF, Lost Phase, Short
Circuit, or Abnormal Output)
52
Designated Data Output 7 (7-bit transmission output)
22
Light Fault (OL, OC1, 2, 3, OP)
53
Light Load Detection Signal
23
Bypass Output #1
54
Heavy Load Detection Signal
24
Bypass Output #2
55
Positive Torque Limit
25
Fan On/Off
56
Negative Torque Limit
26
Jog Active
57
External Rush Suppression Relay Output
27
Terminal Board Operation Command Mode
58
Over Travel
28
Total-Operation-Hours Alarm
59
Positioning Completion
29
Abnormal Communication Alarm (external cause)
60
Earth Fault Alarm
30
Forward/Reverse Operation
61
Low Output Disable Alarm
Summary of Contents for HX7+ ASD
Page 2: ...DN 67017 001 February 2014 HX7 ASD Installation Operation Manual ...
Page 227: ...218 HX7 ASD Installation and Operation Manual Figure 35 200 kVA Sine Wave NEMA 1 Enclosure ...
Page 231: ...222 HX7 ASD Installation and Operation Manual Figure 39 200 kVA Sine Wave NEMA 3R Enclosure ...
Page 235: ...226 HX7 ASD Installation and Operation Manual Figure 43 66 163 kVA 18 Pulse Enclosure ...
Page 236: ...HX7 ASD Installation and Operation Manual 227 Figure 44 200 kVA 18 Pulse Enclosure ...
Page 237: ...228 HX7 ASD Installation and Operation Manual Figure 45 260 518 kVA 18 Pulse Enclosure ...
Page 238: ...HX7 ASD Installation and Operation Manual 229 Figure 46 518 700 kVA 18 Pulse Enclosure ...