HX7+ ASD Installation and Operation Manual
191
86
87
Binary Data Write
— This terminal serves two functions:
1) While operating in the
Use Binary/BCD input
mode, each momentary connection of this terminal to
CC
transfers
the speed/torque
Binary Bit
(0 – MSB)
settings to the motor.
2) The
Motorized Pot
frequency command will be saved during power down or reset by setting
to
Store
and
activating this terminal (Binary Data Write). If the drive is running and the
Binary Data Write
terminal
is active
when an event occurs (Fault, Power off), the
Motorized Pot
frequency command will be restored upon power-up or
reset.
88
89
Motorized Pot Up
(MOP)
— Activation initiates an increase in motor speed for the duration of the activation until
the
Upper Limit
is reached. The
Frequency Mode
setting must be set to
Motorized Pot. Simulation
. The MOP
acceleration rate is determined by the
setting.
90
91
Motorized Pot Down
(MOP)
— Activation initiates a decrease in motor speed for the duration of the activation until
the
Lower Limit
is reached. The
Frequency Mode
setting must be set to
Motorized Pot. Simulation
. The MOP
deceleration rate is determined by the
setting.
92
93
Motorized Pot Clear
— Activation clears the last
Motorized Pot
frequency settings (see
for further
information on this setting).
94
95
Momentary Push Run
— Activation starts the motor.
96
97
Momentary Push Stop
— Activation stops the motor.
98
99
Forward/Reverse
— This setting operates in conjunction with another terminal being set to the
Run/Stop
(100/101)
function. When configured to
Run
(
Run/Stop
terminal active), the activation or deactivation changes the direction of
the motor.
100 101
Run/Stop
— Activation enables the motor to run and deactivation disables the motor.
102 103
Line Power Bypass
— This function operates in conjunction with the
Line Power Switching
frequency setting
). An enabled check box at Program
Terminal Selection
Line Power Switching
(At) and activation of this
terminal enables this function.
Once configured (including activation of this terminal), the frequency setting of
Line Power Switching
(Hz)
establishes the speed at which the drive terminates its output and routes commercial power to the motor.
104 105
Frequency Priority
— Activation allows for the frequency control to be switched from the frequency command
source selected as
Frequency Mode #1
to
Frequency Mode #2
. This function is enabled by setting the
Reference
Priority Selection
to
Frequency Source Priority Switching
and is located at Program
Fundamentals
Standard
Mode Selection
Reference Priority Selection
Frequency Source Priority Switching
.
106 107
VI/II Terminal Priority
— Activation assigns command control to the
VI/II Terminal
and overrides all other
Terminal Board
input so long as the
Command Mode
is set to
Use Terminal Board
.
108 109
Command Terminal Board Priority
— Activation overrides the
FMOD
setting and assigns speed control to the
Terminal Board
.
110 111
Parameter Editing Enabling
— Used with the
CN8 Option
(LED Keypad) only. Activation enables parameter
editing via the
CN8
connector (and keypad).
112 113
Control Switch (torque, position)
— Activation allows for a system change from speed to torque or position as a
function of the V/f setting.
114 115
Deviation Counter Clear
— Activation clears the
Deviation Counter
while operating in the
Position Control
mode.
116 117
Position Control Forward Limit LS
— Activation stops the drive and holds its position. If the connection remains
the drive will time out and trip. This function is normally used for over-travel conditions.
118 119
Position Control Reverse Limit LS
— Activation stops the drive and holds its position. If the connection remains
the drive will time out and trip. This function is normally used for over-travel conditions.
120 121
Light-Load High-Speed Operation Enable
— Activation sets the lower limit of an output frequency range in
which the
Light-Load/High-Speed
function may be used (see
). The
Light-Load/High-Speed
function
accelerates the output frequency of the ASD to the speed setting established in
for the duration of the activation.
122 123
Snap Stop Control Enable
— Not Used.
Note:
NO/NC = Normally Open/Normally Closed. NO/NC selection numbers are used when making system changes via
communications.
Table 14.(Continued) Discrete Input Terminal Assignment Selections and Descriptions.
Sel. No.
Terminal Selection Descriptions
NO NC
otorized Pot
Summary of Contents for HX7+ ASD
Page 2: ...DN 67017 001 February 2014 HX7 ASD Installation Operation Manual ...
Page 227: ...218 HX7 ASD Installation and Operation Manual Figure 35 200 kVA Sine Wave NEMA 1 Enclosure ...
Page 231: ...222 HX7 ASD Installation and Operation Manual Figure 39 200 kVA Sine Wave NEMA 3R Enclosure ...
Page 235: ...226 HX7 ASD Installation and Operation Manual Figure 43 66 163 kVA 18 Pulse Enclosure ...
Page 236: ...HX7 ASD Installation and Operation Manual 227 Figure 44 200 kVA 18 Pulse Enclosure ...
Page 237: ...228 HX7 ASD Installation and Operation Manual Figure 45 260 518 kVA 18 Pulse Enclosure ...
Page 238: ...HX7 ASD Installation and Operation Manual 229 Figure 46 518 700 kVA 18 Pulse Enclosure ...