HX7+ ASD Installation and Operation Manual
Decel #2 Time
Program
Special Control
Accel/Decel #1 – #4
This parameter specifies the time in seconds for the drive to go from the
Maximum Frequency
to 0.0 Hz for the
#2 Deceleration
profile. The accel/
decel pattern may be set using
. The minimum accel/decel time may be set
using
.
This setting is also used to determine the deceleration rate of the
Motorized
Pot
function.
Note:
A deceleration time shorter than the load will allow may cause
nuisance tripping and mechanical stress to loads.
Automatic Accel/Decel
and
Stall
settings
may lengthen the
acceleration time.
Direct Access Number — F501
Parameter Type —
Numerical
Factory Default — (ASD dependent)
Changeable During Run —
Yes
Minimum — 0.1
Maximum — 6000
Units — Seconds