HX7+ ASD Installation and Operation Manual
133
Switching Load Torque During Reverse Run
Program
Special Control
Crane/Hoist Load
While running in reverse, this parameter establishes the threshold torque level
that is used to determine if the
Light-Load High-Speed
) operation may
engage or remain engaged if active.
If the
Light-Load High-Speed
operation is terminated, normal operation
resumes.
Direct Access Number — F338
Parameter Type —
Numerical
Factory Default —
50
Changeable During Run —
Yes
Minimum — 0
Maximum — 250
Units — %
Heavy-Load Torque During Reverse Acceleration
Program
Special Control
Crane/Hoist Load
During reverse acceleration, this parameter establishes the threshold torque
level that is used to determine if the
Light-Load High-Speed
(
) operation
may engage or remain engaged if active.
If the
Light-Load High-Speed
operation is terminated, normal operation
resumes.
Direct Access Number — F339
Parameter Type —
Numerical
Factory Default —
150
Changeable During Run —
Yes
Minimum — 0
Maximum — 250
Units — %
Heavy-Load Torque During Fixed Speed Reverse Run
Program
Special Control
Crane/Hoist Load
While running in reverse at a fixed speed, this parameter establishes the
threshold torque level that is used to determine if the
Light-Load High-Speed
) operation may engage or remain engaged if active.
If the
Light-Load High-Speed
operation is terminated, normal operation
resumes.
Direct Access Number — F340
Parameter Type —
Numerical
Factory Default —
100
Changeable During Run —
Yes
Minimum — 0
Maximum — 250
Units — %
Frequency for Automatic High-Speed Operation at Light-
Load
Program
Special Control
Crane/Hoist Load
This parameter establishes the speed that the ASD will ramp to when operating
in the
Light-Load High-Speed
mode.
Direct Access Number — F341
Parameter Type —
Numerical
Factory Default —
80
Changeable During Run —
Yes
Minimum — 0.00
Maximum — 80.00
Units — %
On-Trip Powerline Switching
Program
Terminal Selection
Line Power Switching
This parameter
Enables/Disables
the
On Trip Powerline Switching
feature.
When enabled, the system is instructed to discontinue using the output of the
drive and to switch to the commercial power in the event of a trip.
Settings:
0 — Disabled
1 — Enabled (box checked)
Direct Access Number — F354
Parameter Type —
Check Box
Factory Default —
Disabled
Changeable During Run —
No
Summary of Contents for HX7+ ASD
Page 2: ...DN 67017 001 February 2014 HX7 ASD Installation Operation Manual ...
Page 227: ...218 HX7 ASD Installation and Operation Manual Figure 35 200 kVA Sine Wave NEMA 1 Enclosure ...
Page 231: ...222 HX7 ASD Installation and Operation Manual Figure 39 200 kVA Sine Wave NEMA 3R Enclosure ...
Page 235: ...226 HX7 ASD Installation and Operation Manual Figure 43 66 163 kVA 18 Pulse Enclosure ...
Page 236: ...HX7 ASD Installation and Operation Manual 227 Figure 44 200 kVA 18 Pulse Enclosure ...
Page 237: ...228 HX7 ASD Installation and Operation Manual Figure 45 260 518 kVA 18 Pulse Enclosure ...
Page 238: ...HX7 ASD Installation and Operation Manual 229 Figure 46 518 700 kVA 18 Pulse Enclosure ...