HX7+ ASD Installation and Operation Manual
127
Over-Voltage Stall
Program
Protection
Stall
This parameter
Enables/Disables
the
Over-Voltage Stall
function. When
enabled, this function causes the drive to extend the decel time when the DC
bus voltage increases due to transient voltage spikes, regeneration, supply
voltage out of specification, etc. in an attempt to reduce the bus voltage.
Settings:
0 — Enabled
1 — Disabled
2 — Enabled (Forced Shorted Deceleration)
Direct Access Number — F305
Parameter Type —
Selection List
Factory Default —
Enabled
Changeable During Run —
Yes
Motor #1 Max Output Voltage
Program
Motor Parameters
Motor Set #1
This parameter sets the maximum value of the output voltage of the drive. The
Motor #1 Maximum Output Voltage
is the
Motor
#1
output voltage at the
Base Frequency
). Regardless of the programmed value, the output
voltage cannot be higher than the input voltage.
The actual output voltage will be influenced by the input voltage of the ASD
and the
Supply Voltage Compensation
setting (
Direct Access Number — F306
Parameter Type —
Numerical
Factory Default — (ASD dependent)
Changeable During Run —
Yes
Minimum — 0.0
Maximum — 600.0
Units — Volts
Supply Voltage Compensation
Program
Protection
Base Frequency Voltage
This parameter
Enables/Disables
the
Voltage Compensation
function. This
function provides an output waveform adjustment that compensates for changes
in the input voltage.
Settings:
0 — Enabled (box checked)
1 — Disabled
Direct Access Number — F307
Parameter Type —
Check Box
Factory Default —
Enabled
Changeable During Run —
No
Dynamic Braking Resistance
Program
Protection
Dynamic Braking
This parameter is used to input the resistive value of the
Dynamic Braking
Resistor
.
For additional information on selecting the proper resistance value for a given
application contact
Toshiba Customer Support Center
.
Note:
Using a resistor value that is too low may result in system
damage.
Direct Access Number — F308
Parameter Type —
Numerical
Factory Default — (ASD dependent)
Changeable During Run —
No
Minimum — 1.0
Maximum — 1000.0
Units —
Dynamic Braking Resistance Capacity
Program
Protection
Dynamic Braking
This parameter is used to input the wattage of the
Dynamic Braking Resistor
.
For additional information on selecting the proper resistor wattage value for a
given application contact
Toshiba Customer Support Center
.
Note:
Using a resistor with a wattage rating that is too low may result
in system damage.
Direct Access Number — F309
Parameter Type —
Numerical
Factory Default — (ASD dependent)
Changeable During Run —
No
Minimum — 0.01
Maximum — 600.0
Units — kW
Summary of Contents for HX7+ ASD
Page 2: ...DN 67017 001 February 2014 HX7 ASD Installation Operation Manual ...
Page 227: ...218 HX7 ASD Installation and Operation Manual Figure 35 200 kVA Sine Wave NEMA 1 Enclosure ...
Page 231: ...222 HX7 ASD Installation and Operation Manual Figure 39 200 kVA Sine Wave NEMA 3R Enclosure ...
Page 235: ...226 HX7 ASD Installation and Operation Manual Figure 43 66 163 kVA 18 Pulse Enclosure ...
Page 236: ...HX7 ASD Installation and Operation Manual 227 Figure 44 200 kVA 18 Pulse Enclosure ...
Page 237: ...228 HX7 ASD Installation and Operation Manual Figure 45 260 518 kVA 18 Pulse Enclosure ...
Page 238: ...HX7 ASD Installation and Operation Manual 229 Figure 46 518 700 kVA 18 Pulse Enclosure ...