106
HX7+ ASD Installation and Operation Manual
RR Speed Frequency #1
Program
Frequency Setting
Speed Reference Setpoints
RR
This parameter is used to set the gain and bias of the
RR
input terminal when
the
RR
terminal is used as the control input while operating in the
Speed
Control
mode.
See
RR Speed Reference #1
(
) for further information on this setting.
This parameter sets
RR Speed Frequency #1
and is the frequency that is
associated with the setting of
RR Speed Reference #1
while operating in the
Speed Control
mode.
Direct Access Number — F211
Parameter Type —
Numerical
Factory Default —
0.0
Changeable During Run —
Yes
Minimum — 0.0
Maximum —
Max. Freq.
Units — Hz
RR Speed Reference #2
Program
Frequency Setting
Speed Reference Setpoints
RR
This parameter is used to set the gain and bias of the
RR
input terminal when
the
RR
terminal is used as the control input while operating in the
Speed
Control
mode or the
Torque Control
mode.
See
RR Speed Reference #1
for further information on this setting when used
for
Speed
control or
Torque
control.
This parameter sets the
RR
input level that is associated with
RR Speed
Frequency #2
while operating in the
Speed
control mode or is associated with
the
RR Torque Reference Setpoint #2
while operating in the
Torque
control
mode.
Direct Access Number — F212
Parameter Type —
Numerical
Factory Default —
100.00
Changeable During Run —
Yes
Minimum — 0.0
Maximum — 100.0
Units — %
RR Speed Frequency #2
Program
Frequency Setting
Speed Reference Setpoints
RR
This parameter is used to set the gain and bias of the
RR
input terminal when
the
RR
terminal is used as the control input while operating in the
Speed
Control
mode.
See
RR Speed Reference #1
for further information on this setting when used
for
Speed
control.
This parameter sets
RR Speed Frequency #2
and is the frequency that is
associated with the setting of
RR Speed Reference #2
while operating in the
Speed Control
mode.
Direct Access Number — F213
Parameter Type —
Numerical
Factory Default —
80.00
Changeable During Run —
Yes
Minimum — 0.0
Maximum —
Max. Freq.
Units — Hz
RR Torque Reference Setpoint #1
Program
Torque Setting
Setpoints
RR
This parameter is used to set the gain and bias of the
RR
input terminal when
the
RR
terminal is used as the control input while operating in the
Torque
Control
mode.
This is accomplished by establishing an associated
V/f
output pattern for a
given
RR
input level.
See
RR Speed Reference #1
for further information on this setting.
This parameter sets
RR
Torque Reference Setpoint #1
and is the output torque
value that is associated with the setting of
RR Speed Reference #1
while
operating in the
Torque
control mode.
Direct Access Number — F214
Parameter Type —
Numerical
Factory Default —
0.00
Changeable During Run —
Yes
Minimum — 0.00
Maximum — 250.0
Units — %
Summary of Contents for HX7+ ASD
Page 2: ...DN 67017 001 February 2014 HX7 ASD Installation Operation Manual ...
Page 227: ...218 HX7 ASD Installation and Operation Manual Figure 35 200 kVA Sine Wave NEMA 1 Enclosure ...
Page 231: ...222 HX7 ASD Installation and Operation Manual Figure 39 200 kVA Sine Wave NEMA 3R Enclosure ...
Page 235: ...226 HX7 ASD Installation and Operation Manual Figure 43 66 163 kVA 18 Pulse Enclosure ...
Page 236: ...HX7 ASD Installation and Operation Manual 227 Figure 44 200 kVA 18 Pulse Enclosure ...
Page 237: ...228 HX7 ASD Installation and Operation Manual Figure 45 260 518 kVA 18 Pulse Enclosure ...
Page 238: ...HX7 ASD Installation and Operation Manual 229 Figure 46 518 700 kVA 18 Pulse Enclosure ...