HX7+ ASD Installation and Operation Manual
105
RR Speed Reference #1
Program
Frequency Setting
Speed Reference Setpoints
RR
This parameter is used to set the gain and bias of the
RR
input terminal when
the
RR
terminal is used as the control input while operating in the
Speed
Control
mode or the
Torque Control
mode.
RR Input Speed Control Setup
Perform the following setup to allow the system to receive
Speed
control input
at the
RR
input terminal:
•
Program
Fundamentals
Standard Mode Selection
Frequency
Mode #1
RR
.
•
Program
Fundamentals
Standard Mode Selection
Command
Mode
Use Terminal Board
.
•
Set
RR Speed Reference #1
) — the input signal level that
represents
RR Speed Frequency #1
.
•
Set
RR Speed Frequency #1
).
•
Set
RR Speed Reference #2
) — the input signal level that
represents
RR Speed Frequency #2.
•
Set
RR Speed Frequency #2
•
Provide a
Run
command (
F
and/or
R
).
Once set, as the
RR
input changes, the output frequency of the ASD will vary
in accordance with the above settings.
This parameter sets
RR Speed Reference #1
and is the input signal level that is
associated with the setting of
RR Speed Frequency #1
while operating in the
Speed Control
mode.
RR Input Torque Control Setup
Perform the following setup to allow the system to receive
Torque
control input
at the
RR
input terminal:
•
Program
Fundamentals
Standard Mode Selection
Frequency
Mode #1
RR
.
•
Program
Fundamentals
Standard Mode Selection
Command
Mode
Use Terminal Board
.
•
Set
RR Speed Reference #1
) — the input signal level that
represents
RR Torque Reference Setpoint #1
.
•
Set
RR Torque Reference Setpoint #1
).
•
Set
RR Speed Reference #2
) — the input signal level that
represents
RR Torque Reference Setpoint #2.
•
Set
RR Torque Reference Setpoint #2
).
•
Provide a
Run
command (
F
and/or
R
).
Once set, as the
RR
input changes, the output torque of the ASD will vary in
accordance with the above settings.
This parameter sets
RR Speed Reference #1
and is the input signal level that is
associated with the setting of
RR Torque Reference Setpoint #1
while
operating in the
Torque Control
mode.
Direct Access Number — F210
Parameter Type —
Numerical
Factory Default —
0.0
Changeable During Run —
Yes
Minimum — 0.0
Maximum — 100.0
Units — %
Frequency Settings
Note:
The speed control
response may be further
trimmed by adjusting
the Bias and Gain
settings.
Torque Settings
Summary of Contents for HX7+ ASD
Page 2: ...DN 67017 001 February 2014 HX7 ASD Installation Operation Manual ...
Page 227: ...218 HX7 ASD Installation and Operation Manual Figure 35 200 kVA Sine Wave NEMA 1 Enclosure ...
Page 231: ...222 HX7 ASD Installation and Operation Manual Figure 39 200 kVA Sine Wave NEMA 3R Enclosure ...
Page 235: ...226 HX7 ASD Installation and Operation Manual Figure 43 66 163 kVA 18 Pulse Enclosure ...
Page 236: ...HX7 ASD Installation and Operation Manual 227 Figure 44 200 kVA 18 Pulse Enclosure ...
Page 237: ...228 HX7 ASD Installation and Operation Manual Figure 45 260 518 kVA 18 Pulse Enclosure ...
Page 238: ...HX7 ASD Installation and Operation Manual 229 Figure 46 518 700 kVA 18 Pulse Enclosure ...