182
HX7+ ASD Installation and Operation Manual
LOD Control and Stopping Method
Program
Special Control
Low Output Disable
This parameter
Enables/Disables
the
Low Output Disable
function and, if
enabled, selects a stopping method.
Settings:
0 — Disabled
1 — Enabled — Decel Stop
2 — Enabled — Coast Stop
Direct Access Number — F731
Parameter Type —
Selection List
Factory Default —
Disabled
Changeable During Run —
Yes
LOD Start Level (Hz)
Program
Special Control
Low Output Disable
The
Low Output Disable Start Level
sets the output frequency threshold that,
if exceeded, will initiate the
LOD
function if properly configured.
Direct Access Number — F732
Parameter Type —
Numerical
Factory Default —
0.0
Changeable During Run —
Yes
Minimum — 0.0
Maximum —
Max. Freq.
Units — Hz
LOD Start Time
Program
Special Control
Low Output Disable
The
Low Output Disable Start Time
sets the amount of time that the
LOD
Start Level
criteria must be met and maintained for the
LOD
function to be
initiated.
Direct Access Number — F733
Parameter Type —
Numerical
Factory Default —
0.0
Changeable During Run —
Yes
Minimum — 0.0
Maximum — 3600.0
Units — Seconds
LOD Setpoint Boost (Hz)
Program
Special Control
Low Output Disable
The
Low Output Disable
feature adds the user-input frequency value to the
commanded frequency.
Direct Access Number — F734
Parameter Type —
Numerical
Factory Default —
0.0
Changeable During Run —
Yes
Minimum — 0.0
Maximum —
Max. Freq.
Units — Hz
LOD Boost Time
Program
Special Control
Low Output Disable
The
Low Output Disable
Boost Time
sets the on-time timer for the
LOD
Boost
function.
Once expired, the
LOD Boost
function ceases.
Direct Access Number — F735
Parameter Type —
Numerical
Factory Default —
0.0
Changeable During Run —
Yes
Minimum — 0.0
Maximum — 3600.0
Units — Seconds
LOD Feedback Level (Hz)
Program
Special Control
Low Output Disable
The
Low Output Disable Feedback Level
sets a frequency level that, until the
output of the ASD drops below this setting, the
Restart Delay Timer
does not
start.
Direct Access Number — F736
Parameter Type —
Numerical
Factory Default —
0.0
Changeable During Run —
Yes
Minimum — 0.0
Maximum —
Max. Freq.
Units — Hz
Summary of Contents for HX7+ ASD
Page 2: ...DN 67017 001 February 2014 HX7 ASD Installation Operation Manual ...
Page 227: ...218 HX7 ASD Installation and Operation Manual Figure 35 200 kVA Sine Wave NEMA 1 Enclosure ...
Page 231: ...222 HX7 ASD Installation and Operation Manual Figure 39 200 kVA Sine Wave NEMA 3R Enclosure ...
Page 235: ...226 HX7 ASD Installation and Operation Manual Figure 43 66 163 kVA 18 Pulse Enclosure ...
Page 236: ...HX7 ASD Installation and Operation Manual 227 Figure 44 200 kVA 18 Pulse Enclosure ...
Page 237: ...228 HX7 ASD Installation and Operation Manual Figure 45 260 518 kVA 18 Pulse Enclosure ...
Page 238: ...HX7 ASD Installation and Operation Manual 229 Figure 46 518 700 kVA 18 Pulse Enclosure ...