HX7+ ASD Installation and Operation Manual
121
Jog Run Frequency
Program
Frequency Setting
Jog Settings
This parameter sets the output frequency of the drive during a
Jog
.
Jogging
is
the term used to describe turning the motor on for small increments of time and
is used when precise positioning of motor-driven equipment is required.
Enabling the
Jog Window
allows for the
Manual Jog
window to be among the
screens accessed during repeated
MON/PRG
entries. This screen must be
displayed when
Jogging
using the keypad.
The
Jog
function may be initiated from the keypad or remotely via the
Terminal Board
or
using
Communications
(for further information on using
Communications
for
Jogging
, see the
Communications
manual).
To perform a
Jog
, set this parameter (
) to the desired
Jog
frequency.
Select a
Jog Stop
method (
).
Jog Setup Using the Keypad
To initiate a
Jog
from the keypad perform the following:
1. Place a check in the
Enable Jog Window
box (Program
Frequency
Setting
Jog Settings
Enable Jog Window
).
Note:
The
Jog Window
must be displayed on the keypad to perform the
Jog
function using the keypad.
2.Press
MON/PRG
to access the
Jog Window
.
3.Using the
Up/Down
arrow keys of the keypad, select
Reverse
or
Forward
.
4.Place the system in the
Local
mode (
Local|Remote
LED is on).
5.Press and hold the
Run
key for the desired
Jog
duration.
Jog Setup Using the Terminal Board
To initiate a
Jog
from the
Terminal Board
perform the following:
1. Assign a discrete input terminal to the
Jog
).
2.Assign a discrete input terminal to the
F
(
Forward
) function (and
Reverse
).
3.Provide a
Forward
and/or
Reverse
command from the
Terminal Board
.
4.From the
Jog Window
, use the
Up/Down
arrow keys of the keypad to
select
Reverse
or
Forward
(Program
Frequency Setting
Jog
Settings
Enable Jog Window
). Press
MON/PRG
to access the
Jog
Window
.
5.Place the system in the
Remote
mode (
Local|Remote
LED is off).
6.Connect the assigned
Jog
terminal (from step
) to
CC
for the desired
Jog
duration.
Direct Access Number — F260
Parameter Type —
Numerical
Factory Default —
0.00
Changeable During Run —
Yes
Minimum — 0.00
Maximum — 20.00
Units — Hz
Summary of Contents for HX7+ ASD
Page 2: ...DN 67017 001 February 2014 HX7 ASD Installation Operation Manual ...
Page 227: ...218 HX7 ASD Installation and Operation Manual Figure 35 200 kVA Sine Wave NEMA 1 Enclosure ...
Page 231: ...222 HX7 ASD Installation and Operation Manual Figure 39 200 kVA Sine Wave NEMA 3R Enclosure ...
Page 235: ...226 HX7 ASD Installation and Operation Manual Figure 43 66 163 kVA 18 Pulse Enclosure ...
Page 236: ...HX7 ASD Installation and Operation Manual 227 Figure 44 200 kVA 18 Pulse Enclosure ...
Page 237: ...228 HX7 ASD Installation and Operation Manual Figure 45 260 518 kVA 18 Pulse Enclosure ...
Page 238: ...HX7 ASD Installation and Operation Manual 229 Figure 46 518 700 kVA 18 Pulse Enclosure ...