82
HX7+ ASD Installation and Operation Manual
ST Signal Selection
Program
Terminal Selection
Input Special
This parameter is used to set the operation of the
Standby
(
ST
) control terminal
or any terminal configured as the
ST
terminal.
Settings:
0 — ST-to-CC Required
1 — ST-to-CC Not Required
2 — Interlock with F/R Terminal
The setting
ST-to-CC Required
enables the ASD for operation so long as the
control terminal
ST
is connected to
CC
via a jumper, contact, or other means.
The
ST-to-CC Not Required
setting allows the ASD to operate without the
ST
-to-
CC
connection. The control terminal
ST
may be configured for other
functions.
The
Interlock with F/R Terminal
setting configures the
F
(
Forward
) and
R
(
Reverse
) control terminals for the secondary function of
Standby
. Closing a
set of contacts to either
F
or
R
will cause the ASD to accelerate the motor to the
programmed setpoint of
F
or
R
. Opening the
F
and
R
contact will disable the
ASD and the motor will coast to a stop. The control terminal
ST
may be
configured for other functions.
Direct Access Number — F103
Parameter Type —
Selection List
Factory Default —
ST – CC Required
Changeable During Run —
No
R/F Priority Selection
Program
Terminal Selection
Input Special
The
R/F Priority Selection
determines the operation of the ASD if both the
R
and
F
control terminals are activated.
Settings:
0 — Reverse
1 — Suspend
The waveforms below depict the motor response for all combinations of the
F
and
R
terminal settings if the
Reverse
option is chosen.
The
Suspend
setting will decelerate the motor to a stop regardless of the
rotation direction when both the
F
and
R
control terminals are activated.
Direct Access Number — F105
Parameter Type —
Selection List
Factory Default —
Reverse
Changeable During Run —
No
Summary of Contents for HX7+ ASD
Page 2: ...DN 67017 001 February 2014 HX7 ASD Installation Operation Manual ...
Page 227: ...218 HX7 ASD Installation and Operation Manual Figure 35 200 kVA Sine Wave NEMA 1 Enclosure ...
Page 231: ...222 HX7 ASD Installation and Operation Manual Figure 39 200 kVA Sine Wave NEMA 3R Enclosure ...
Page 235: ...226 HX7 ASD Installation and Operation Manual Figure 43 66 163 kVA 18 Pulse Enclosure ...
Page 236: ...HX7 ASD Installation and Operation Manual 227 Figure 44 200 kVA 18 Pulse Enclosure ...
Page 237: ...228 HX7 ASD Installation and Operation Manual Figure 45 260 518 kVA 18 Pulse Enclosure ...
Page 238: ...HX7 ASD Installation and Operation Manual 229 Figure 46 518 700 kVA 18 Pulse Enclosure ...