HX7+ ASD Installation and Operation Manual
79
Preset Speed #1
Program
Pattern Run
Preset Speeds
Up to 15 output frequency values that fall within the
Lower Limit
and the
Upper Limit
range may be programmed into the drive and output as a
Preset
Speed
. This parameter assigns an output frequency to binary number 0001 and
is identified as
Preset Speed #1
. The binary number is applied to
S1
–
S4
of the
Terminal Board
to output the
Preset Speed
.
Perform the following setup to allow the system to receive
Preset Speed
control input at the
S1 – S4
terminals:
1.
Program
Fundamentals
Standard Mode Selection
Use Terminal
Board
.
2.
Program
Terminal Selection
Input Terminals
S1
(set to
Preset
Speed Command 1
; LSB of 4-bit count). Repeat for
S2
–
S4
(MSB of 4-bit
count) as
Preset Speed Command 2
–
4
, respectively (all
Normally
Open
).
Note:
The default setting of
S4
is
EOff
, but this terminal may be re-
assigned as the MSB.
3.
Program
Frequency Setting
Preset Speeds
1
(press
Enter
twice
and set an output frequency as
Preset Speed #1
; repeat for
Preset Speeds 2
–
15
as required).
4.
Program
Frequency Setting
Preset Speed Mode
Use Speed Modes
(
Enable/Disable
)
.
When
Enabled
, the direction, accel/decel, and torque settings of the
Preset Speed
being run are used.
When
Disabled
, only the speed setting of the
Preset Speed
being run is
used.
5.
Place the system in the
Remote
mode (
Local|Remote
LED Off).
6.
Provide a
Run
command (connect
F
and/or
R
to
CC
).
Connect
S1
to
CC
to run
Preset Speed #1
(
S1
to
CC
= 0001 binary).
With
S1
–
S4
configured to output
Preset Speeds
–
), 0001 – 1111
may be applied to
S1 – S4
of the
Terminal Board
to run the associated
Preset
Speed
. If bidirectional operation is required,
F
and
R
must be connected to
CC
,
and
Use Speed Modes
must be enabled at
.
With
S1
being the least significant bit of a binary count, the
S1 – S4
settings
will produce the programmed speed settings as indicated in the Preset Speed
Truth Table to the right.
Preset Speeds
are also used in the
Pattern Run
mode.
Direct Access Number — F018
Parameter Type —
Numerical
Factory Default —
0.0
Changeable During Run —
Yes
Minimum —
Lower Limit
)
Maximum —
Upper Limit
Units — Hz
Preset Speed Truth Table.
Preset Speed #2
Program
Pattern Run
Preset Speeds
This parameter assigns an output frequency to binary number 0010 and is
identified as
Preset Speed #2
. The binary number is applied to
S1
–
S4
of the
Terminal Board
to output the
Preset Speed
(see
for further information
on this parameter).
Direct Access Number — F019
Parameter Type —
Numerical
Factory Default —
0.0
Changeable During Run —
Yes
Minimum —
Lower Limit
)
Maximum —
Upper Limit
Units — Hz
Preset
S4
MSB
S3
S2
S1
LSB
Output
1
0
0
0
1
2
0
0
1
0
3
0
0
1
1
4
0
1
0
0
5
0
1
0
1
6
0
1
1
0
7
0
1
1
1
8
1
0
0
0
9
1
0
0
1
10
1
0
1
0
11
1
0
1
1
12
1
1
0
0
13
1
1
0
1
14
1
1
1
0
15
1
1
1
1
Note:
1 = Terminal connected to
CC
.
Preset
S4
MSB
S3
S2
S1
LSB
Output
1
0
0
0
1
F018
2
0
0
1
0
3
0
0
1
1
4
0
1
0
0
5
0
1
0
1
6
0
1
1
0
7
0
1
1
1
8
1
0
0
0
9
1
0
0
1
10
1
0
1
0
11
1
0
1
1
12
1
1
0
0
13
1
1
0
1
14
1
1
1
0
15
1
1
1
1
Note:
1 = Terminal connected to
CC
.
Summary of Contents for HX7+ ASD
Page 2: ...DN 67017 001 February 2014 HX7 ASD Installation Operation Manual ...
Page 227: ...218 HX7 ASD Installation and Operation Manual Figure 35 200 kVA Sine Wave NEMA 1 Enclosure ...
Page 231: ...222 HX7 ASD Installation and Operation Manual Figure 39 200 kVA Sine Wave NEMA 3R Enclosure ...
Page 235: ...226 HX7 ASD Installation and Operation Manual Figure 43 66 163 kVA 18 Pulse Enclosure ...
Page 236: ...HX7 ASD Installation and Operation Manual 227 Figure 44 200 kVA 18 Pulse Enclosure ...
Page 237: ...228 HX7 ASD Installation and Operation Manual Figure 45 260 518 kVA 18 Pulse Enclosure ...
Page 238: ...HX7 ASD Installation and Operation Manual 229 Figure 46 518 700 kVA 18 Pulse Enclosure ...