126
HX7+ ASD Installation and Operation Manual
Number of Retries
Program
Protection
Retry/Restart
After a trip has occurred, this parameter sets the number of times that an
automatic system restart is attempted for a qualified trip.
The trip conditions listed below will not initiate the automatic
Retry/Restart
function:
•
U, V, W Phase Short Circuit,
•
DBR Resistor Overcurrent,
•
Input Phase Loss (Input Phase Failure),
•
Output Phase Loss (Output Phase Failure),
•
Overcurrent During Acceleration (Startup Overcurrent),
•
Earth Fault (Ground Fault),
•
EMG (Emergency Off),
•
EEPROM Data Fault (EEPROM Fault),
•
Flash Memory/Gate Array/RAM-ROM Fault,
•
CPU Fault,
•
Communication Error,
•
Option Fault,
•
Output Current Protection Fault,
•
Sink/Source Setting Error,
•
Over-Speed Error, or
•
Key Error.
General Safety Information on pg. 1
for further
information on this setting.
Direct Access Number — F303
Parameter Type —
Numerical
Factory Default —
00
Changeable During Run —
Yes
Minimum — 00
Maximum — 10
Dynamic Braking Enable
Program
Protection
Dynamic Braking
This parameter
Enables/Disables
the
Dynamic Braking
system.
Settings:
0 — Enabled with Overload
1 — Disabled
Dynamic Braking
Dynamic Braking
uses the inertial energy of the load to produce a braking
force or it may be used to reduce the bus voltage in an attempt to preclude an
over-voltage trip during deceleration. The inertial energy of the load drives the
rotor and induces a current into the stator of the motor.
The induced stator current (energy) is dissipated through a resistive load. The
resistive load is connected across terminals
PA
and
PB
(non-polarized). Using a
low-value, high-wattage resistance as a load for the generated current, the
resistive load dissipates the induced energy. The dissipated energy is the energy
that would otherwise have caused the rotor to continue to rotate.
Dynamic Braking
helps to slow the load quickly; it cannot act as a holding
brake.
The
Dynamic Braking
function may be setup and enabled by connecting a
braking resistor from terminal
PA
to
PB
of the drive and providing the proper
, and
For additional information on selecting the proper resistance value for a given
application contact the
Toshiba Customer Support Center
.
Direct Access Number — F304
Parameter Type —
Selection List
Factory Default —
Disabled
Changeable During Run —
No
Summary of Contents for HX7+ ASD
Page 2: ...DN 67017 001 February 2014 HX7 ASD Installation Operation Manual ...
Page 227: ...218 HX7 ASD Installation and Operation Manual Figure 35 200 kVA Sine Wave NEMA 1 Enclosure ...
Page 231: ...222 HX7 ASD Installation and Operation Manual Figure 39 200 kVA Sine Wave NEMA 3R Enclosure ...
Page 235: ...226 HX7 ASD Installation and Operation Manual Figure 43 66 163 kVA 18 Pulse Enclosure ...
Page 236: ...HX7 ASD Installation and Operation Manual 227 Figure 44 200 kVA 18 Pulse Enclosure ...
Page 237: ...228 HX7 ASD Installation and Operation Manual Figure 45 260 518 kVA 18 Pulse Enclosure ...
Page 238: ...HX7 ASD Installation and Operation Manual 229 Figure 46 518 700 kVA 18 Pulse Enclosure ...