72
HX7+ ASD Installation and Operation Manual
Direct Access Parameter Information
The
HX7+ ASD
allows the user direct access to the motor control functions. The functions listed below
have an associated
Parameter Number
which accesses its setting. There are two ways in which the menu
may be used to allow access to the motor-control parameters for modification: Program
applicable
menu path
or Program
Direct Access
applicable parameter number
.
Both methods access the
parameter via the
Program
mode. Once accessed, the parameter may be viewed or changed.
The
Program
mode allows the user to develop
an application-specific motor control profile. Motor
control functions may be set to accommodate specific power and timing requirements for a given
application. The configurable parameters of the
Program
mode are listed and described below.
Note:
The setup procedures included within this section may require a
Reset
before performing the procedure.
Application-specific settings may then be performed. The pre-Reset conditions may be saved (see
).
Direct Access Parameters/Numbers
Automatic Accel/Decel #1
Program
Fundamentals
This parameter
Enables/Disables
the ability of the ASD to adjust the
acceleration and deceleration rates in accordance with the applied load
automatically.
The adjusted acceleration and deceleration times range from 12.5% to 800% of
the programmed values for
Acceleration Time #1
) and
Deceleration
Time #1
).
Settings:
0 — Disabled
1 — Enabled (box checked)
Note:
The motor and the load must be connected prior to selecting
Automatic Accel/Decel
.
Direct Access Number — F000
Parameter Type —
Check Box
Factory Default —
Disabled
Changeable During Run —
No
Command Mode Selection
Program
Fundamentals
Standard Mode Selection
The
Command Mode Selection
establishes the source of the command input
for the ASD.
Command
inputs include
Run
,
Stop
,
Forward
, etc. The
Override
feature may supersede the
Command Mode Selection
setting (see
Command Mode and Frequency Mode Control on pg. 46
).
Settings:
0 — Use Terminal Board
1 — Use
CN8 Option (LED Keypad)
2 — Use Common Serial (TTL)
3 — Use RS232/RS485
4 — Use Communication Card
Direct Access Number — F003
Parameter Type —
Selection List
Factory Default —
Use Terminal Board
Changeable During Run —
No
Summary of Contents for HX7+ ASD
Page 2: ...DN 67017 001 February 2014 HX7 ASD Installation Operation Manual ...
Page 227: ...218 HX7 ASD Installation and Operation Manual Figure 35 200 kVA Sine Wave NEMA 1 Enclosure ...
Page 231: ...222 HX7 ASD Installation and Operation Manual Figure 39 200 kVA Sine Wave NEMA 3R Enclosure ...
Page 235: ...226 HX7 ASD Installation and Operation Manual Figure 43 66 163 kVA 18 Pulse Enclosure ...
Page 236: ...HX7 ASD Installation and Operation Manual 227 Figure 44 200 kVA 18 Pulse Enclosure ...
Page 237: ...228 HX7 ASD Installation and Operation Manual Figure 45 260 518 kVA 18 Pulse Enclosure ...
Page 238: ...HX7 ASD Installation and Operation Manual 229 Figure 46 518 700 kVA 18 Pulse Enclosure ...