Frequency Point Selection
Program
Communication
Communication Reference Adjust
This parameter enables the communications reference for scaling by selecting
an input type.
See
for further information on this setting.
Note:
Scaling the communications signal is not required for all
applications.
Changes made to this parameter require that the power be cycled (Off then On)
for the changes to take effect.
Settings:
0 — Disabled
1 — Common Serial (TTL)
2 — RS232/RS485
3 — Communication Card
Direct Access Number — F810
Parameter Type —
Selection List
Factory Default —
Disabled
Changeable During Run —
Yes
Communications Speed Reference #1
Program
Communication
Communication Reference Adjust
When enabled at
, this parameter is used to allow the user to set the gain
and bias of the speed control input to the drive when the speed control signal is
received via the source selected at
Communications Input Speed Control Setup
Perform the following setup to allow the system to receive control input via
Communications:
•
Set
Communications Speed Reference #1
(
) — the input signal
that represents
BIN Speed Frequency #1
.
•
Set
Communications Speed Frequency #1
(
).
•
Set
Communications Speed Reference #2
— the input signal
that represents
BIN Speed Frequency #2
.
•
Set
Communications Speed Frequency #2
(
).
•
Provide a
Run
command (
F
and/or
R
).
Once set, as the input signal value changes, the output frequency of the drive
will vary in accordance with the above settings.
This parameter sets the
Communications Speed Reference #1
input value that
represents
Communications Speed Frequency #1
. This value is entered as 0 to
100% of the
Communications Speed Reference #1
input value range.
Changes made to this parameter require that the power be cycled (Off then On)
for the changes to take effect.
Direct Access Number — F811
Parameter Type —
Numerical
Factory Default —
0.00
Changeable During Run —
Yes
Minimum — 0.00
Maximum — 100.0
Units — %
Summary of Contents for HX7+ ASD
Page 2: ...DN 67017 001 February 2014 HX7 ASD Installation Operation Manual ...
Page 227: ...218 HX7 ASD Installation and Operation Manual Figure 35 200 kVA Sine Wave NEMA 1 Enclosure ...
Page 231: ...222 HX7 ASD Installation and Operation Manual Figure 39 200 kVA Sine Wave NEMA 3R Enclosure ...
Page 235: ...226 HX7 ASD Installation and Operation Manual Figure 43 66 163 kVA 18 Pulse Enclosure ...
Page 236: ...HX7 ASD Installation and Operation Manual 227 Figure 44 200 kVA 18 Pulse Enclosure ...
Page 237: ...228 HX7 ASD Installation and Operation Manual Figure 45 260 518 kVA 18 Pulse Enclosure ...
Page 238: ...HX7 ASD Installation and Operation Manual 229 Figure 46 518 700 kVA 18 Pulse Enclosure ...