28
HX7+ ASD Installation and Operation Manual
I/O and Control
The
HX7+ ASD
can be controlled by several input types and combinations thereof, as well as operate
within a wide range of output frequency and voltage levels. This section discusses the ASD control
methods and supported I/O functions.
The
Terminal Board
supports discrete and analog I/O functions and is shown in
.
lists the names and the default settings of the input and output terminals of the
Terminal Board
.
See the section titled
Terminal Descriptions on pg. 29
for an expanded description of each terminal.
Note:
Set the
Command Mode
to
Terminal Board
to use the input control lines of the
Terminal Board
for command input (Program
Fundamental
Standard Mode
Selection
Command Mode
Terminal Board). Output lines of the
Terminal
Board
need not be selected to enable the output. However, output lines may be set to
a user-selected function.
shows the typical connection diagram for the HX7+ ASD system.
Table 6. Terminal Board Terminal Names and Functions.
Default Term.
Setting
Input/Output
Default Function
(also see
Terminal Descriptions on pg. 29
)
Circuit Config.
ST
Discrete Input
Connect to CC
to activate
(Sink mode)
Switching
applies to
discrete input
terminals only.
Standby
— Multifunctional programmable discrete input. Activation
required for normal ASD operation.
RES
Reset
— Multifunctional programmable discrete input. Resets a faulted
ASD.
F
Forward
— Multifunctional programmable discrete input.
R
Reverse
— Multifunctional programmable discrete input.
S1
Preset Speed 1
— Multifunctional programmable discrete input.
S2
Preset Speed 2
— Multifunctional programmable discrete input.
S3
Preset Speed 3
— Multifunctional programmable discrete input.
S4
Emergency Off
— Multifunctional programmable discrete input.
RR
Analog Input
RR
— Multifunction programmable analog input
(0.0 to 10 volt input — 0 to 80 Hz output).
RX
RX
— Multifunctional programmable analog input
(-10 to +10 VDC input — -80 to +80 Hz output).
II
II
— Multifunctional programmable analog input (4 [0] to 20 mADC
input — 0 to 80 Hz output).
VI
VI
— Multifunctional programmable analog input
(0 to 10 VDC input — 0 to 80 Hz output).
AM
Analog Output
Produces an output current that is proportional to the magnitude of the
function assigned to this terminal.
FM
OUT1 (C-A)
Switched
Output
Low Frequency
— Programmable contact (N.O.).
OUT2 (C-A)
Reach Frequency
— Programmable contact (N.O.).
FLA
Fault relay (N.O.).
FLB
Fault relay (N.C.).
FLC
Fault relay (Common).
FP
Pulsed Output
Frequency Pulse
— an output pulse train that has a frequency which is
based on the output frequency of the ASD.
P24
DC Output
24 VDC @ 50 mA output.
PP
PP
— 10.0 VDC voltage source for the external potentiometer.
CC
—
Return for analog and discrete input terminals.
DO NOT
connect to
Earth Gnd.
Summary of Contents for HX7+ ASD
Page 2: ...DN 67017 001 February 2014 HX7 ASD Installation Operation Manual ...
Page 227: ...218 HX7 ASD Installation and Operation Manual Figure 35 200 kVA Sine Wave NEMA 1 Enclosure ...
Page 231: ...222 HX7 ASD Installation and Operation Manual Figure 39 200 kVA Sine Wave NEMA 3R Enclosure ...
Page 235: ...226 HX7 ASD Installation and Operation Manual Figure 43 66 163 kVA 18 Pulse Enclosure ...
Page 236: ...HX7 ASD Installation and Operation Manual 227 Figure 44 200 kVA 18 Pulse Enclosure ...
Page 237: ...228 HX7 ASD Installation and Operation Manual Figure 45 260 518 kVA 18 Pulse Enclosure ...
Page 238: ...HX7 ASD Installation and Operation Manual 229 Figure 46 518 700 kVA 18 Pulse Enclosure ...