Motor Type
Program
Motor Parameters
Motor Settings
This parameter identifies the type of motor being used.
Settings:
0 — Toshiba EQP III TEFC
1 — Toshiba EQP III ODP
2 — Toshiba EPACT TEFC
3 — Toshiba EPACT ODP
4 — Other Motor
Direct Access Number — F413
Parameter Type —
Selection List
Factory Default —
Toshiba EQP III
TEFC
Changeable During Run —
No
Motor Constant 3 Enable
Program
Motor Parameters
Vector Motor Model
This parameter
Enables/Disables
tuning of
Motor Constant 3
during an
Autotune
.
Settings:
0 — Disabled
1 — Enabled (box checked)
Direct Access Number — F414
Parameter Type —
Check Box
Factory Default —
Enable
Changeable During Run —
No
Torque Command
Program
Torque Setting
Torque Control
When operating in the
Torque Control
mode, this parameter allows the user to
select the source of the torque command signal.
Settings:
1 — VI/II
2 — RR
3 — RX
4 — RX2 (option)
5 — CN8 Option (LED Keypad)
6 — Binary/BCD Input
7 — Common Serial (TTL)
8 — RS232/RS485
9 — Communication Card
Direct Access Number — F420
Parameter Type —
Selection List
Factory Default —
RX
Changeable During Run —
Yes
Torque Command Filter
Program
Torque Setting
Torque Control
This parameter reduces the motor vibration caused by large-inertia loads. A
small value will have a great effect while an increased value will have a lesser
effect.
Direct Access Number — F421
Parameter Type —
Numerical
Factory Default —
200.0
Changeable During Run —
Yes
Minimum — 10.0
Maximum — 200.0
Summary of Contents for HX7+ ASD
Page 2: ...DN 67017 001 February 2014 HX7 ASD Installation Operation Manual ...
Page 227: ...218 HX7 ASD Installation and Operation Manual Figure 35 200 kVA Sine Wave NEMA 1 Enclosure ...
Page 231: ...222 HX7 ASD Installation and Operation Manual Figure 39 200 kVA Sine Wave NEMA 3R Enclosure ...
Page 235: ...226 HX7 ASD Installation and Operation Manual Figure 43 66 163 kVA 18 Pulse Enclosure ...
Page 236: ...HX7 ASD Installation and Operation Manual 227 Figure 44 200 kVA 18 Pulse Enclosure ...
Page 237: ...228 HX7 ASD Installation and Operation Manual Figure 45 260 518 kVA 18 Pulse Enclosure ...
Page 238: ...HX7 ASD Installation and Operation Manual 229 Figure 46 518 700 kVA 18 Pulse Enclosure ...