HX7+ ASD Installation and Operation Manual
Lower Deviation Limits
Program
Feedback Parameters
Feedback Settings
This parameter determines the maximum amount that the feedback may
decrease the output signal.
Direct Access Number — F365
Parameter Type —
Numerical
Factory Default —
50.00
Changeable During Run —
Yes
Minimum — 0.00
Maximum — 50.00
Units — %
Feedback Settings Differential (D) Gain
Program
Feedback Parameters
Feedback Settings
This parameter determines the degree that the
Differential
function affects the
output signal. The larger the value entered here, the more pronounced the affect
of the differential function for a given feedback signal level.
Direct Access Number — F366
Parameter Type —
Numerical
Factory Default —
0.00
Changeable During Run —
Yes
Minimum — 0.0
Maximum — 2.55
Number of PG Input Pulses
Program
Feedback Parameters
PG Settings
This parameter is used to set the end-of-travel range when using an encoder on
a motor-driven positioning system (e.g., hoist/crane, etc.).
Direct Access Number — F367
Parameter Type —
Numerical
Factory Default —
500
Changeable During Run —
No
Minimum — 1
Maximum — 9999
Units — Pulse Count
PG Input Phases
Program
Feedback Parameters
PG Settings
This parameter determines the type of information that is supplied by the phase
encoder.
Settings:
1 — Speed
2 — Speed and Direction
Direct Access Number — F368
Parameter Type —
Selection List
Factory Default —
2
Changeable During Run —
No
Minimum — 1
Maximum — 2
Units — Phase Count
PG Disconnect Detection
Program
Feedback Parameters
PG Settings
This parameter
Enables/Disables
the system’s monitoring of the PG connection
status when using encoders with line driver outputs.
Note:
The ASD-Multicom-J option board is required to use this feature.
Settings:
0 — Disabled
1 — Enabled
Direct Access Number — F369
Parameter Type —
Selection List
Factory Default —
Disabled
Changeable During Run —
No
Electronic Gear Setting
Program
Feedback Parameters
PG Settings
This parameter sets the number of pulses per revolution when using a shaft-
mounted encoder and the
PG
Option Board
for closed loop speed control.
Direct Access Number — F370
Parameter Type —
Numerical
Factory Default —
1000
Changeable During Run —
No
Minimum — 100
Maximum — 4000
Summary of Contents for HX7+ ASD
Page 2: ...DN 67017 001 February 2014 HX7 ASD Installation Operation Manual ...
Page 227: ...218 HX7 ASD Installation and Operation Manual Figure 35 200 kVA Sine Wave NEMA 1 Enclosure ...
Page 231: ...222 HX7 ASD Installation and Operation Manual Figure 39 200 kVA Sine Wave NEMA 3R Enclosure ...
Page 235: ...226 HX7 ASD Installation and Operation Manual Figure 43 66 163 kVA 18 Pulse Enclosure ...
Page 236: ...HX7 ASD Installation and Operation Manual 227 Figure 44 200 kVA 18 Pulse Enclosure ...
Page 237: ...228 HX7 ASD Installation and Operation Manual Figure 45 260 518 kVA 18 Pulse Enclosure ...
Page 238: ...HX7 ASD Installation and Operation Manual 229 Figure 46 518 700 kVA 18 Pulse Enclosure ...