202
HX7+ ASD Installation and Operation Manual
Overvoltage During Deceleration
• Deceleration time is too short.
• DBR value is too high.
• DBR required (DBR setup required).
• Stall protection is disabled.
• 3-phase input voltage is out of specification.
• Input reactance required.
Overvoltage During Run
• Load fluctuations.
• 3-Phase input voltage out of specification.
PG Type/Connection Error
• ASD is configured to receive a signal from a shaft-mounted encoder and no signal
is being received while running.
• Disconnection at the Encoder circuit.
• Motor is stopped and is generating torque via torque limit control.
• ASD is not configured properly.
Phantom Fault
• In a multiple ASD configuration a faulted ASD signals the remaining ASDs that a
fault has occurred and shuts down the non-faulted ASDs.
Position Deviation Error
• Operating in the
Position Control
mode and the resulting position exceeds the
setting.
RAM Fault
• Internal RAM malfunction.
ROM Fault
• Internal ROM malfunction.
Sink/Source Setting Error
• Improperly positioned
Sink/Source
jumper on the control board or on an option
device.
•
Sink/Source
configuration of an option device is incorrect.
Torque Proving Fault
• Lift-First Pulse Count (F743) adjustment required.
Typeform Error
• Firmware information (typeform) loaded into the
Gate Driver
board is
inconsistent with the device in which the firmware is being used.
• The
Gate Driver
board has been replaced.
• The
Gate Driver
board is defective.
U Phase Short Circuit
• Low impedance at the U lead of the ASD output.
V Phase Short Circuit
• Low impedance at the V lead of the ASD output.
W Phase Short Circuit
• Low impedance at the W lead of the ASD output.
Note:
The event that caused the Trip(s) must be corrected or must decrease to less than the threshold
value required to cause the trip to allow for a Reset to be recognized. In the event of multiple
active trips, the trip displayed will remain until all faults are corrected and all trips are cleared.
Fault Screen Display
Possible Causes
Summary of Contents for HX7+ ASD
Page 2: ...DN 67017 001 February 2014 HX7 ASD Installation Operation Manual ...
Page 227: ...218 HX7 ASD Installation and Operation Manual Figure 35 200 kVA Sine Wave NEMA 1 Enclosure ...
Page 231: ...222 HX7 ASD Installation and Operation Manual Figure 39 200 kVA Sine Wave NEMA 3R Enclosure ...
Page 235: ...226 HX7 ASD Installation and Operation Manual Figure 43 66 163 kVA 18 Pulse Enclosure ...
Page 236: ...HX7 ASD Installation and Operation Manual 227 Figure 44 200 kVA 18 Pulse Enclosure ...
Page 237: ...228 HX7 ASD Installation and Operation Manual Figure 45 260 518 kVA 18 Pulse Enclosure ...
Page 238: ...HX7 ASD Installation and Operation Manual 229 Figure 46 518 700 kVA 18 Pulse Enclosure ...