HX7+ ASD Installation and Operation Manual
179
Analog 1 Terminal Adjustment
Program
Meter Terminal Adjustment
Analog 1
This parameter adjusts the coefficient of the
Analog 1
circuit to obtain an
output that corresponds with a known input.
This function is used in the calibration of external signal measuring devices
(DVM, counters, etc.).
Direct Access Number — F673
Parameter Type —
Numerical
Factory Default —
512
Changeable During Run —
Yes
Minimum — 1
Maximum — 1280
Analog 2 Terminal Setting
Program
Meter Terminal Adjustment
Analog 2
This parameter sets the
Analog 2
multifunction programmable terminal to 1 of
33 possible functions and is available on the
ASD Multicom
option board only.
Possible assignments for this output terminal are listed in
.
Direct Access Number — F674
Parameter Type —
Selection List
Factory Default —
Post-compensation
Frequency
Changeable During Run —
Yes
Analog 2 Terminal Adjustment
Program
Meter Terminal Adjustment
Analog 2
This parameter adjusts the coefficient of the circuit to obtain an output that
corresponds with a known input.
This function is used in the calibration of external signal measuring devices
(DVM, counters, etc.).
Direct Access Number — F675
Parameter Type —
Numerical
Factory Default —
512
Changeable During Run —
Yes
Minimum — 1
Maximum — 1280
FP Terminal Setting
Program
Terminal Selection
FP
This parameter commands the multifunction programmable
FP
terminal to
monitor the value of 1 of 33 possible system functions. As the monitored
function changes in magnitude or frequency, the pulse count of the
FP
output
pulse train changes in direct proportion to changes in the monitored function.
As the monitored value goes up so does the pulse count of the
FP
output.
Note:
The duty cycle of the output pulse train remains at 65 ±5.0 µS.
Possible assignments for this output terminal are listed in
.
Direct Access Number — F676
Parameter Type —
Selection List
Factory Default —
Output Frequency
Changeable During Run —
Yes
FP Terminal Adjustment
Program
Terminal Selection
FP
This parameter sets the full-scale reading of the
FP Terminal
. The full-scale
reading of the monitored variable selected in
may be set here.
Direct Access Number — F677
Parameter Type —
Numerical
Factory Default —
3.840
Changeable During Run —
Yes
Minimum — 1.000
Maximum — 43.200
Units — kHz
Display Units for Voltage and Current
Program
Utility Parameters
Display Units
This parameter sets the unit of measurement for current and voltage values
displayed on the keypad.
Settings:
0 — %
1 — V/A
Direct Access Number — F701
Parameter Type —
Selection List
Factory Default — %
Changeable During Run —
Yes
Summary of Contents for HX7+ ASD
Page 2: ...DN 67017 001 February 2014 HX7 ASD Installation Operation Manual ...
Page 227: ...218 HX7 ASD Installation and Operation Manual Figure 35 200 kVA Sine Wave NEMA 1 Enclosure ...
Page 231: ...222 HX7 ASD Installation and Operation Manual Figure 39 200 kVA Sine Wave NEMA 3R Enclosure ...
Page 235: ...226 HX7 ASD Installation and Operation Manual Figure 43 66 163 kVA 18 Pulse Enclosure ...
Page 236: ...HX7 ASD Installation and Operation Manual 227 Figure 44 200 kVA 18 Pulse Enclosure ...
Page 237: ...228 HX7 ASD Installation and Operation Manual Figure 45 260 518 kVA 18 Pulse Enclosure ...
Page 238: ...HX7 ASD Installation and Operation Manual 229 Figure 46 518 700 kVA 18 Pulse Enclosure ...