HX7+ ASD Installation and Operation Manual
131
Drooping Reference
Program
Feedback Parameters
Drooping Control
This parameter sets the method to be used in determining the output torque
while operating in the
Drooping Control
mode.
Settings:
0 — Total Torque Calculated by the Detection Current.
1 — Torque without Acc/Dec Torque Calculated by Detection Current.
2 — Total Torque Calculated by the Command Current.
3 — Torque without Acc/Dec Torque Calculated by the Command Current.
Direct Access Number — F327
Parameter Type —
Selection List
Factory Default —
Total torque
calculated by the detection current
Changeable During Run —
Yes
Light-Load High-Speed Operation Selection
Program
Special Control
Crane/Hoist Load
This parameter enables the
Light-Load High-Speed
function by selecting an
operating mode. The
Light-Load High-Speed
function accelerates the output
frequency of the ASD from the programmed speed to the setting established in
This parameter may be disabled.
If either of the other selections are made and configured, and after the criteria of
are met, the
Light-Load High-Speed
function is enabled and this
parameter determines the operating mode of the
Light-Load High-Speed
function.
Settings:
0 — Disabled
1 — Reserved
2 — Automatic Enable - Automatic Speed (
3 — Automatic Enable - Preset Speed (Preset ID
Bin
is OR’ed w/1000
Bin
)
4 — Discrete Enable - Automatic Speed (
) (see item 60 of
)
5 — Discrete Enable - Preset Speed (Preset ID
Bin
is OR’ed w/1000
Bin
) (see
item 60 of
)
Direct Access Number — F330
Parameter Type —
Selection List
Factory Default —
Disabled
Changeable During Run —
No
Minimum — 30.0
Maximum —
Upper Limit
(
Units — Hz
Light-Load High-Speed Operation Switching Lower-Limit
Frequency
Program
Special Control
Crane/Hoist Load
This parameter sets an output frequency threshold that, once surpassed, allows
the
Light-Load High-Speed
function to be used.
The
Light-Load High-Speed
function may be used if the frequency threshold
) and the following conditions are met:
1)
Light-Load High-Speed Operation Enable
2) The output torque is less than the setting established in
when reaching
the frequency setting here.
Direct Access Number — F331
Parameter Type —
Numerical
Factory Default —
40.00
Changeable During Run —
Yes
Minimum — 30.0
Maximum —
Upper Limit
(
Units — Hz
Summary of Contents for HX7+ ASD
Page 2: ...DN 67017 001 February 2014 HX7 ASD Installation Operation Manual ...
Page 227: ...218 HX7 ASD Installation and Operation Manual Figure 35 200 kVA Sine Wave NEMA 1 Enclosure ...
Page 231: ...222 HX7 ASD Installation and Operation Manual Figure 39 200 kVA Sine Wave NEMA 3R Enclosure ...
Page 235: ...226 HX7 ASD Installation and Operation Manual Figure 43 66 163 kVA 18 Pulse Enclosure ...
Page 236: ...HX7 ASD Installation and Operation Manual 227 Figure 44 200 kVA 18 Pulse Enclosure ...
Page 237: ...228 HX7 ASD Installation and Operation Manual Figure 45 260 518 kVA 18 Pulse Enclosure ...
Page 238: ...HX7 ASD Installation and Operation Manual 229 Figure 46 518 700 kVA 18 Pulse Enclosure ...