98
HX7+ ASD Installation and Operation Manual
Custom V/f Five-Point Setting #1 Voltage
Program
Special Control
V/f Five-Point Setting
The
Custom V/f Five-Point Setting #1 Voltage
establishes the percentage of
the output voltage that is to be associated with the frequency setting of
(
Custom V/f Five-Point Setting #1 Frequency
).
See
for additional information on custom V/f curves.
Direct Access Number — F191
Parameter Type —
Numerical
Factory Default —
0.00
Changeable During Run —
No
Minimum — 0.0
Maximum — 100.0
Units — %
Custom V/f Five-Point Setting #2 Frequency
Program
Special Control
V/f Five-Point Setting
The
Custom V/f Five Point Setting #2 Frequency
sets the frequency to be
associated with parameter
(
Custom V/f Five Point Setting #2 Voltage
).
See
for additional information on custom V/f curves.
Direct Access Number — F192
Parameter Type —
Numerical
Factory Default —
0.0
Changeable During Run —
No
Minimum — 0.0
Maximum — 299
Units — Hz
Custom V/f Five-Point Setting #2 Voltage
Program
Special Control
V/f Five-Point Setting
The
Custom V/f Five-Point Setting #2 Voltage
establishes the percentage of
the output voltage that is to be associated with the frequency setting of
(
Custom V/f Five Point Setting #2 Frequency
).
See
for additional information on custom V/f curves.
Direct Access Number — F193
Parameter Type —
Numerical
Factory Default —
0.0
Changeable During Run —
No
Minimum — 0.0
Maximum — 100.0
Units — %
Custom V/f Five-Point Setting #3 Frequency
Program
Special Control
V/f Five-Point Setting
The
Custom V/f Five Point Setting #3 Frequency
sets the frequency to be
associated with parameter
(
Custom V/f Five Point Setting #3 Voltage
).
See
for additional information on custom V/f curves.
Direct Access Number — F194
Parameter Type —
Numerical
Factory Default —
0.0
Changeable During Run —
No
Minimum — 0.0
Maximum — 299
Units — Hz
Custom V/f Five-Point Setting #3 Voltage
Program
Special Control
V/f Five-Point Setting
The
Custom V/f Five-Point Setting #3 Voltage
establishes the percentage of
the output voltage that is to be associated with the frequency setting of
(
Custom V/f Five Point Setting #3 Frequency
).
See
for additional information on custom V/f curves.
Direct Access Number — F195
Parameter Type —
Numerical
Factory Default —
0.0
Changeable During Run —
No
Minimum — 0.0
Maximum — 100.0
Units — %
Custom V/f Five-Point Setting #4 Frequency
Program
Special Control
V/f Five-Point Setting
The
Custom V/f Five Point Setting #4 Frequency
sets the frequency to be
associated with parameter
(
Custom V/f Five Point Setting #4 Voltage
).
See
for additional information on custom V/f curves.
Direct Access Number — F196
Parameter Type —
Numerical
Factory Default —
0.0
Changeable During Run —
No
Minimum — 0.0
Maximum — 299
Units — Hz
Summary of Contents for HX7+ ASD
Page 2: ...DN 67017 001 February 2014 HX7 ASD Installation Operation Manual ...
Page 227: ...218 HX7 ASD Installation and Operation Manual Figure 35 200 kVA Sine Wave NEMA 1 Enclosure ...
Page 231: ...222 HX7 ASD Installation and Operation Manual Figure 39 200 kVA Sine Wave NEMA 3R Enclosure ...
Page 235: ...226 HX7 ASD Installation and Operation Manual Figure 43 66 163 kVA 18 Pulse Enclosure ...
Page 236: ...HX7 ASD Installation and Operation Manual 227 Figure 44 200 kVA 18 Pulse Enclosure ...
Page 237: ...228 HX7 ASD Installation and Operation Manual Figure 45 260 518 kVA 18 Pulse Enclosure ...
Page 238: ...HX7 ASD Installation and Operation Manual 229 Figure 46 518 700 kVA 18 Pulse Enclosure ...