Ridethrough Time
Program
Protection
Retry/Restart
In the event of a momentary power outage, this parameter determines the length
of the
Ridethrough
time. During a
Ridethrough
, regenerative energy is used
to maintain the control circuitry settings; it is not used to drive the motor.
The
Ridethrough
will be maintained for the number of seconds set using this
parameter.
Note:
The actual
Ridethrough Time
is load-dependent.
Direct Access Number — F310
Parameter Type —
Numerical
Factory Default —
2.00
Changeable During Run —
Yes
Minimum — 0.00
Maximum — 320.0
Units — Seconds
Disable Forward Run/Disable Reverse Run
Program
Frequency Setting
Forward/Reverse Disable
This parameter
Enables/Disables
the
Forward Run
or
Reverse Run
mode.
If either direction is disabled (box checked), commands received for the
disabled direction will not be recognized.
If both directions are disabled (both boxes checked), the received direction
command will determine the direction of the motor rotation.
Settings:
0 — Disabled
1 — Enabled
Direct Access Number — F311
Parameter Type —
Check Box
Factory Default —
Disabled
Changeable During Run —
No
Scan Rate
Program
Protection
Retry/Restart
In the event of a momentary power outage, the output signal of the drive will
cease. Upon restoration of power, the drive will output a low-level signal that
will be used to determine the rotation speed of the rotor.
The low-level signal will start scanning the motor at
FH
and decrease until it
reaches 0.0 Hz or it matches the signal produced by the turning rotor. Once the
rate of rotation is determined, the drive will provide the normal output to
engage the motor from its present speed.
This parameter determines the rate at which the scanning signal goes from
FH
for additional information on this parameter.
Direct Access Number — F312
Parameter Type —
Numerical
Factory Default — (ASD dependent)
Changeable During Run —
No
Minimum — 0.50
Maximum — 2.50
Lock-on Rate
Program
Protection
Retry/Restart
After a momentary power outage, the ASD may have to startup into a spinning
motor. The
Lock On Rate
is the difference between the time that the RPM of
the motor is determined by the ASD and the time that the ASD outputs a drive
signal to the motor.
See
for additional information on this parameter.
Direct Access Number — F313
Parameter Type —
Numerical
Factory Default — (ASD dependent)
Changeable During Run —
No
Minimum — 0.50
Maximum — 2.50
Summary of Contents for HX7+ ASD
Page 2: ...DN 67017 001 February 2014 HX7 ASD Installation Operation Manual ...
Page 227: ...218 HX7 ASD Installation and Operation Manual Figure 35 200 kVA Sine Wave NEMA 1 Enclosure ...
Page 231: ...222 HX7 ASD Installation and Operation Manual Figure 39 200 kVA Sine Wave NEMA 3R Enclosure ...
Page 235: ...226 HX7 ASD Installation and Operation Manual Figure 43 66 163 kVA 18 Pulse Enclosure ...
Page 236: ...HX7 ASD Installation and Operation Manual 227 Figure 44 200 kVA 18 Pulse Enclosure ...
Page 237: ...228 HX7 ASD Installation and Operation Manual Figure 45 260 518 kVA 18 Pulse Enclosure ...
Page 238: ...HX7 ASD Installation and Operation Manual 229 Figure 46 518 700 kVA 18 Pulse Enclosure ...