156
HX7+ ASD Installation and Operation Manual
Accel/Decel Pattern #2
Program
Special Control
Accel/Decel #1 – #4
This parameter enables a user-selected preprogrammed output profile that
controls the acceleration and deceleration pattern for the
#2 Accel/Decel
parameter.
Settings:
0 — Linear
1 — S-Pattern 1
2 — S-Pattern 2
Direct Access Number — F503
Parameter Type —
Selection List
Factory Default —
Linear
Changeable During Run —
Yes
Accel/Decel Group
No path available (Direct Access Only)
While operating using the
CN8 Option
(LED Keypad)
this parameter
selects the accel/decel profile to be used during a multiple-accel/decel profile
configuration. The accel/decel setting for selections 1 – 4 may be found at
, and
, respectively.
Settings:
1 — Group 1
2 — Group 2
3 — Group 3
4 — Group 4
Note:
Press
ESC
from the
screen to access this
parameter.
Direct Access Number — F504
Parameter Type —
Selection List
Factory Default —
1
Changeable During Run —
Yes
Acc/Dec Switching Frequency #1
Program
Special Control
Accel/Decel Special
This parameter sets the frequency at which the acceleration control is switched
from the
Accel #1
profile to the
Accel #2
profile during a multiple-acceleration
profile configuration.
Direct Access Number — F505
Parameter Type —
Numerical
Factory Default —
0.00
Changeable During Run —
Yes
Minimum — 0.00
Maximum —
Max. Freq.
Units — Hz
S-Pattern Lower Limit Adjustment
Program
Special Control
Accel/Decel Special
Sets the lower limit of
S-pattern 1
and
2
.
Direct Access Number — F506
Parameter Type —
Numerical
Factory Default —
25.00
Changeable During Run —
Yes
Minimum — 0.00
Maximum — 50.00
Units — %
S-Pattern Upper Limit Adjustment
Program
Special Control
Accel/Decel Special
Sets the upper limit frequency of
S-pattern 1
and
2
.
Direct Access Number — F507
Parameter Type —
Numerical
Factory Default —
25.00
Changeable During Run —
Yes
Minimum — 0.00
Maximum — 50.00
Units — %
Summary of Contents for HX7+ ASD
Page 2: ...DN 67017 001 February 2014 HX7 ASD Installation Operation Manual ...
Page 227: ...218 HX7 ASD Installation and Operation Manual Figure 35 200 kVA Sine Wave NEMA 1 Enclosure ...
Page 231: ...222 HX7 ASD Installation and Operation Manual Figure 39 200 kVA Sine Wave NEMA 3R Enclosure ...
Page 235: ...226 HX7 ASD Installation and Operation Manual Figure 43 66 163 kVA 18 Pulse Enclosure ...
Page 236: ...HX7 ASD Installation and Operation Manual 227 Figure 44 200 kVA 18 Pulse Enclosure ...
Page 237: ...228 HX7 ASD Installation and Operation Manual Figure 45 260 518 kVA 18 Pulse Enclosure ...