158
HX7+ ASD Installation and Operation Manual
Accel #4 Time
Program
Special Control
Accel/Decel #1 – #4
This parameter specifies the time in seconds for the drive to go from 0.0 Hz to
the
Maximum Frequency
for the
#4 Acceleration
profile. The accel/decel
pattern may be set using
. The minimum accel/decel time may be set using
Note:
An acceleration time shorter than the load will allow may cause
nuisance tripping and mechanical stress to loads.
Automatic Accel/Decel
and
Stall
settings
may lengthen the
acceleration time.
Direct Access Number — F514
Parameter Type —
Numerical
Factory Default — (ASD dependent)
Changeable During Run —
Yes
Minimum — 0.1
Maximum — 6000
Units — Seconds
Decel #4 Time
Program
Special Control
Accel/Decel #1 – #4
This parameter specifies the time in seconds for the drive to go from the
Maximum Frequency
to 0.0 Hz for the
#4 Deceleration
profile. The accel/
decel pattern may be set using
. The minimum accel/decel time may be set
using
.
Note:
A deceleration time shorter than the load will allow may cause
nuisance tripping and mechanical stress to loads.
Automatic Accel/Decel
and
Stall
settings
may lengthen the
deceleration time.
Direct Access Number — F515
Parameter Type —
Numerical
Factory Default — (ASD dependent)
Changeable During Run —
Yes
Minimum — 0.1
Maximum — 6000
Units — Seconds
Accel/Decel Pattern #4
Program
Special Control
Accel/Decel #1 – #4
This parameter enables a user-selected preprogrammed output profile that
controls the acceleration and deceleration pattern for the
#4 Accel/Decel
parameter.
Settings:
0 — Linear
1 — S-Pattern 1
2 — S-Pattern 2
Direct Access Number — F516
Parameter Type —
Selection List
Factory Default —
Linear
Changeable During Run —
Yes
Accel/Decel Switching Frequency #3
Program
Special Control
Accel/Decel Special
This parameter sets the frequency at which the acceleration control is switched
from the
Accel #3
profile to the
Accel #4
profile during a multiple-acceleration
profile configuration.
Direct Access Number — F517
Parameter Type —
Numerical
Factory Default —
0.00
Changeable During Run —
Yes
Minimum — 0.00
Maximum —
Max. Freq.
Units — Hz
Summary of Contents for HX7+ ASD
Page 2: ...DN 67017 001 February 2014 HX7 ASD Installation Operation Manual ...
Page 227: ...218 HX7 ASD Installation and Operation Manual Figure 35 200 kVA Sine Wave NEMA 1 Enclosure ...
Page 231: ...222 HX7 ASD Installation and Operation Manual Figure 39 200 kVA Sine Wave NEMA 3R Enclosure ...
Page 235: ...226 HX7 ASD Installation and Operation Manual Figure 43 66 163 kVA 18 Pulse Enclosure ...
Page 236: ...HX7 ASD Installation and Operation Manual 227 Figure 44 200 kVA 18 Pulse Enclosure ...
Page 237: ...228 HX7 ASD Installation and Operation Manual Figure 45 260 518 kVA 18 Pulse Enclosure ...
Page 238: ...HX7 ASD Installation and Operation Manual 229 Figure 46 518 700 kVA 18 Pulse Enclosure ...