HX7+ ASD Installation and Operation Manual
147
Power Running (Driving) Torque Limit #1
Program
Torque Setting
Torque Limit Settings
This parameter determines the source of the control signal for the positive
torque limit setting. If
Setting
is selected, the value set at
Power Running Torque Limit #1
input.
Settings:
1 — VI/II
2 — RR
3 — RX
4 — RX2 (option)
5 — Setting (of
Direct Access Number — F440
Parameter Type —
Selection List
Factory Default —
Setting
Changeable During Run —
Yes
Driving Torque Limit #1 Setting
Program
Torque Setting
Manual Torque Limit
This parameter provides a value for the
Power Running Torque Limit #1
setting if
Setting
. This value provides the positive torque
upper limit for the #1 motor.
Direct Access Number — F441
Parameter Type —
Numerical
Factory Default —
250.0
Changeable During Run —
Yes
Minimum — 0.00
Maximum — 250.0
Units — %
Regeneration Torque Limit #1
Program
Torque Setting
Torque Limit Settings
This parameter determines the source of the
Regenerative Torque Limit
control signal. If
Setting
parameter.
Settings:
1 — VI/II
2 — RR
3 — RX
4 — RX2 (option)
5 — Setting (of
Direct Access Number — F442
Parameter Type —
Selection List
Factory Default —
Setting
Changeable During Run —
Yes
Regeneration Torque Limit Setting #1
Program
Torque Setting
Torque Limit Settings
Manual Settings
This parameter provides a value to be used as the
Regeneration Torque Limit
#1
if
Setting
.
Direct Access Number — F443
Parameter Type —
Numerical
Factory Default —
250.0
Changeable During Run —
Yes
Minimum — 0.00
Maximum — 250.0
Units — %
Driving Torque Limit #2
Program
Torque Setting
Manual Torque Limit
This parameter is used to set the positive torque upper limit for the #2 motor
profile when multiple motors are controlled by a single drive or when a single
motor is to be controlled by multiple profiles.
Direct Access Number — F444
Parameter Type —
Numerical
Factory Default —
250.0
Changeable During Run —
Yes
Minimum — 0.00
Maximum — 250.0
Units — %
Summary of Contents for HX7+ ASD
Page 2: ...DN 67017 001 February 2014 HX7 ASD Installation Operation Manual ...
Page 227: ...218 HX7 ASD Installation and Operation Manual Figure 35 200 kVA Sine Wave NEMA 1 Enclosure ...
Page 231: ...222 HX7 ASD Installation and Operation Manual Figure 39 200 kVA Sine Wave NEMA 3R Enclosure ...
Page 235: ...226 HX7 ASD Installation and Operation Manual Figure 43 66 163 kVA 18 Pulse Enclosure ...
Page 236: ...HX7 ASD Installation and Operation Manual 227 Figure 44 200 kVA 18 Pulse Enclosure ...
Page 237: ...228 HX7 ASD Installation and Operation Manual Figure 45 260 518 kVA 18 Pulse Enclosure ...
Page 238: ...HX7 ASD Installation and Operation Manual 229 Figure 46 518 700 kVA 18 Pulse Enclosure ...