HX7+ ASD Installation and Operation Manual
Jog Stop Control
Program
Frequency Setting
Jog Settings
This parameter sets the stopping method used while operating in the
Jog
mode.
Settings:
0 — Deceleration Stop
1 — Coast Stop
2 — DC Injection Braking Stop
Direct Access Number — F261
Parameter Type —
Selection List
Factory Default —
Deceleration Stop
Changeable During Run —
Yes
Jump Frequency #1
Program
Special Control
Jump Frequencies
In conjunction with parameter
, this parameter establishes a user-defined
frequency range: the
Jump Frequency
and a plus-or-minus value. During
acceleration, the output frequency of the drive will hold at the frequency of the
lower level of the
Jump Frequency
range until the programmed acceleration
ramp reaches the upper level of the
Jump Frequency
range. Then, the output
frequency of the drive will accelerate to the upper level of the
Jump
Frequency
range and continue upward as programmed.
During deceleration, the output frequency of the drive will hold at the
frequency of the upper level of the
Jump Frequency
range until the
programmed deceleration ramp reaches the lower level of the
Jump Frequency
range. Then, the output frequency of the drive will decelerate to the lower level
of the
Jump Frequency
range and continue downward as programmed.
Once set up and enabled, it is on in all control modes.
User-selected frequencies may be jumped to avoid the negative effects of
mechanical resonance.
Direct Access Number — F270
Parameter Type —
Numerical
Factory Default —
0.00
Changeable During Run —
Yes
Minimum — 0.00
Maximum —
Max. Freq.
Units — Hz
Jump Frequency #1 Bandwidth
Program
Special Control
Jump Frequencies
This parameter establishes a plus-or-minus value for
Jump Frequency #1
(see
Direct Access Number — F271
Parameter Type —
Numerical
Factory Default —
0.00
Changeable During Run —
Yes
Minimum — 0.00
Maximum — 30.00
Units — Hz
Jump Frequency #2
Program
Special Control
Jump Frequencies
Same as
Jump Frequency #1
) and is used when multiple frequencies are
to be jumped (see the plus-or-minus value setting at
). When multiple
jump frequencies overlap, the system will recognize the lowest and the highest
frequencies as one jump range.
Direct Access Number — F272
Parameter Type —
Numerical
Factory Default —
0.00
Changeable During Run —
Yes
Minimum — 0.00
Maximum —
Max. Freq.
Units — Hz
Jump Frequency #2 Bandwidth
Program
Special Control
Jump Frequencies
This parameter establishes a plus-or-minus value for
Jump Frequency #2
).
Direct Access Number — F273
Parameter Type —
Numerical
Factory Default —
0.00
Changeable During Run —
Yes
Minimum — 0.00
Maximum — 30.0
Units — Hz
Summary of Contents for HX7+ ASD
Page 2: ...DN 67017 001 February 2014 HX7 ASD Installation Operation Manual ...
Page 227: ...218 HX7 ASD Installation and Operation Manual Figure 35 200 kVA Sine Wave NEMA 1 Enclosure ...
Page 231: ...222 HX7 ASD Installation and Operation Manual Figure 39 200 kVA Sine Wave NEMA 3R Enclosure ...
Page 235: ...226 HX7 ASD Installation and Operation Manual Figure 43 66 163 kVA 18 Pulse Enclosure ...
Page 236: ...HX7 ASD Installation and Operation Manual 227 Figure 44 200 kVA 18 Pulse Enclosure ...
Page 237: ...228 HX7 ASD Installation and Operation Manual Figure 45 260 518 kVA 18 Pulse Enclosure ...
Page 238: ...HX7 ASD Installation and Operation Manual 229 Figure 46 518 700 kVA 18 Pulse Enclosure ...