HX7+ ASD Installation and Operation Manual
135
Feedback Source
Program
Feedback Parameters
Feedback Settings
This parameter
Enables/Disables
PID
feedback control. When enabled, this
parameter determines the source of the motor-control feedback.
Settings:
0 — PID Control Disabled
1 — VI/II
2 — RR
3 — RX
4 — RX2 (option)
Proportional-Integral-Derivative
(PID) — A closed-loop control technique
that seeks error minimization by reacting to three values: One that is
proportional to the error, one that is representative of the error, and one that is
representative of the rate of change of the error.
Direct Access Number — F360
Parameter Type —
Selection List
Factory Default —
Control Disabled
Changeable During Run —
Yes
Feedback Source Delay Filter
Program
Feedback Parameters
Feedback Settings
This parameter determines the delay in the ASD output response to the motor-
control feedback signal (signal source is selected at
Direct Access Number — F361
Parameter Type —
Numerical
Factory Default —
0
Changeable During Run —
Yes
Minimum — 0
Maximum — 255
Proportional (P) Gain
Program
Feedback Parameters
Feedback Settings
This parameter determines the degree that the
Proportional
function affects the
output signal. The larger the value entered here, the quicker the drive responds
to changes in feedback.
Direct Access Number — F362
Parameter Type —
Numerical
Factory Default —
0.10
Changeable During Run —
Yes
Minimum — 0.01
Maximum — 100.0
Integral (I) Gain
Program
Feedback Parameters
Feedback Settings
This parameter determines the degree that the
Integral
function affects the
output signal. The smaller the value here, the more pronounced the effect of the
integral function on the output signal.
Direct Access Number — F363
Parameter Type —
Numerical
Factory Default —
0.10
Changeable During Run —
Yes
Minimum — 0.01
Maximum — 100.0
Upper Deviation Limits
Program
Feedback Parameters
Feedback Settings
This parameter determines the maximum amount that the feedback may
increase the output signal.
Direct Access Number — F364
Parameter Type —
Numerical
Factory Default —
50.00
Changeable During Run —
Yes
Minimum — 0.00
Maximum — 50.00
Units — %
Summary of Contents for HX7+ ASD
Page 2: ...DN 67017 001 February 2014 HX7 ASD Installation Operation Manual ...
Page 227: ...218 HX7 ASD Installation and Operation Manual Figure 35 200 kVA Sine Wave NEMA 1 Enclosure ...
Page 231: ...222 HX7 ASD Installation and Operation Manual Figure 39 200 kVA Sine Wave NEMA 3R Enclosure ...
Page 235: ...226 HX7 ASD Installation and Operation Manual Figure 43 66 163 kVA 18 Pulse Enclosure ...
Page 236: ...HX7 ASD Installation and Operation Manual 227 Figure 44 200 kVA 18 Pulse Enclosure ...
Page 237: ...228 HX7 ASD Installation and Operation Manual Figure 45 260 518 kVA 18 Pulse Enclosure ...
Page 238: ...HX7 ASD Installation and Operation Manual 229 Figure 46 518 700 kVA 18 Pulse Enclosure ...