90
HX7+ ASD Installation and Operation Manual
OUT7 Terminal Assignment
Program
Terminal Selection
Output Terminal
This parameter sets the functionality of the
OUT7
terminals to 1 of the 62
possible functions that are listed in
.
The on and off delay times of the
OUT7
terminals may be adjusted to provide
more response time to the device that is connected to the output terminals.
In addition, the output terminals must be specified as
Normally Open
or
Normally Closed
.
Direct Access Number — F136
Parameter Type —
Selection List
Factory Default —
Over-Current
Prealarm
Changeable During Run —
No
F Input Terminal Delay
Program
Terminal Selection
In Terminal Delays
This parameter delays the response of the ASD to any change in the
F
terminal
input by the programmed value.
The delay may be increased to provide additional electrical noise immunity or
to prevent the ASD from responding to contact bounce or chatter.
Direct Access Number — F140
Parameter Type —
Numerical
Factory Default —
8.0
Changeable During Run —
No
Minimum — 2.0
Maximum — 200.0
Units — mS
R Input Terminal Delay
Program
Terminal Selection
In Terminal Delays
This parameter delays the response of the drive to any change in the
R
terminal
input by the programmed value (see waveforms at
The delay may be increased to provide additional electrical noise immunity or
to prevent the ASD from responding to contact bounce or chatter.
Direct Access Number — F141
Parameter Type —
Numerical
Factory Default —
8.0
Changeable During Run —
No
Minimum — 2.0
Maximum — 200.0
Units — mS
ST Input Terminal Delay
Program
Terminal Selection
In Terminal Delays
This parameter delays the response of the drive to any change in the
ST
terminal input by the programmed value (see waveforms at
).
The delay may be increased to provide additional electrical noise immunity or
to prevent the ASD from responding to contact bounce or chatter.
Direct Access Number — F142
Parameter Type —
Numerical
Factory Default —
8.0
Changeable During Run —
No
Minimum — 2.0
Maximum — 200.0
Units — mS
RES Input Terminal Delay
Program
Terminal Selection
In Terminal Delays
This parameter delays the response of the drive to any change in the
RES
terminal input by the programmed value (see waveforms at
).
The delay may be increased to provide additional electrical noise immunity or
to prevent the ASD from responding to contact bounce or chatter.
Direct Access Number — F143
Parameter Type —
Numerical
Factory Default —
8.0
Changeable During Run —
No
Minimum — 2.0
Maximum — 200.0
Units — mS
Summary of Contents for HX7+ ASD
Page 2: ...DN 67017 001 February 2014 HX7 ASD Installation Operation Manual ...
Page 227: ...218 HX7 ASD Installation and Operation Manual Figure 35 200 kVA Sine Wave NEMA 1 Enclosure ...
Page 231: ...222 HX7 ASD Installation and Operation Manual Figure 39 200 kVA Sine Wave NEMA 3R Enclosure ...
Page 235: ...226 HX7 ASD Installation and Operation Manual Figure 43 66 163 kVA 18 Pulse Enclosure ...
Page 236: ...HX7 ASD Installation and Operation Manual 227 Figure 44 200 kVA 18 Pulse Enclosure ...
Page 237: ...228 HX7 ASD Installation and Operation Manual Figure 45 260 518 kVA 18 Pulse Enclosure ...
Page 238: ...HX7 ASD Installation and Operation Manual 229 Figure 46 518 700 kVA 18 Pulse Enclosure ...