HX7+ ASD Installation and Operation Manual
203
Viewing Trip Information
In the event that the condition causing an
Alarm
does not return to the normal operating level within a
specified time, the ASD
Faults
and a
Trip
is incurred.
When a trip occurs, the resultant error information may be viewed either from the
screen
(Program
Monitor Setup
Trip History), the
screen (Program
Monitor
Setup
Trip Monitor From ASD), or from the
Monitor
screen.
Trip History
The
Trip History
screen records the system parameters for up to 101 trips (RTC option required). The
recorded trips are numbered from zero to 100. Once the
Trip History
record reaches trip number 100, the
oldest recorded trip will be deleted with each new record stored (first-in first-out). The
Trip #
field may be
selected and scrolled through to view the recorded trip information for a given trip number. The monitored
parameters are listed in
At-trip Recorded Parameters
(parameter readings at the time that
the trip occurred).
Table 20. HX7+ ASD Trip History Record Parameters (RTC option required).
At-trip Recorded Parameters
Trip records that are assigned zero and one are comprised of the full list of monitored parameters (32).
Trip records 2 – 18 are comprised of parameters 1 – 16. Trip records 19 – 100 are comprised of
parameters 1 – 7.
1) Trip Number
9) Bus Voltage
17) Torque Reference
25) ASD Load
2) Trip Type
10) Discrete Input Status
18) Torque Current
26) DBR Load
3) Time and Date
11) OUT1/OUT2/FL Status
19) Excitation Current
27) Input Power
4) Frequency at Trip
12) Timer
20) PID Value
28) Output Power
5) Output Current
13) Post Compensation Frequency
21) Motor Overload
29) Peak Current
6) Output Voltage
14) Feedback (inst.)
22) ASD Overload
30) Peak Voltage
7) Direction
15) Feedback (1 sec.)
23) DBR Overload
31) PG Speed
8) Frequency Reference
16) Torque
24) Motor Load
32) PG Position
Summary of Contents for HX7+ ASD
Page 2: ...DN 67017 001 February 2014 HX7 ASD Installation Operation Manual ...
Page 227: ...218 HX7 ASD Installation and Operation Manual Figure 35 200 kVA Sine Wave NEMA 1 Enclosure ...
Page 231: ...222 HX7 ASD Installation and Operation Manual Figure 39 200 kVA Sine Wave NEMA 3R Enclosure ...
Page 235: ...226 HX7 ASD Installation and Operation Manual Figure 43 66 163 kVA 18 Pulse Enclosure ...
Page 236: ...HX7 ASD Installation and Operation Manual 227 Figure 44 200 kVA 18 Pulse Enclosure ...
Page 237: ...228 HX7 ASD Installation and Operation Manual Figure 45 260 518 kVA 18 Pulse Enclosure ...
Page 238: ...HX7 ASD Installation and Operation Manual 229 Figure 46 518 700 kVA 18 Pulse Enclosure ...