HX7+ ASD Installation and Operation Manual
141
Preset Speed Direction #13
Program
Pattern Run
Preset Speeds
Determines the forward/reverse setting for the
#13 Preset Speed
Settings:
0 — Forward
1 — Reverse
Direct Access Number — F393
Parameter Type —
Selection List
Factory Default —
Forward
Changeable During Run —
No
Preset Speed Direction #14
Program
Pattern Run
Preset Speeds
Determines the forward/reverse setting for the
#14 Preset Speed
Settings:
0 — Forward
1 — Reverse
Direct Access Number — F394
Parameter Type —
Selection List
Factory Default —
Forward
Changeable During Run —
No
Preset Speed Direction #15
Program
Pattern Run
Preset Speeds
Determines the forward/reverse setting for the
#15 Preset Speed
Settings:
0 — Forward
1 — Reverse
Direct Access Number — F395
Parameter Type —
Selection List
Factory Default —
Forward
Changeable During Run —
No
Vector Motor Model Autotune Command
Program
Motor Parameters
Vector Motor Model
This parameter sets the
Autotune
command status.
Settings:
0 — Autotune Disabled
1 — Reset Motor Defaults
2 — Enable Autotune on Run Command
Direct Access Number — F400
Parameter Type —
Selection List
Factory Default —
Autotune Disabled
Changeable During Run —
No
Vector Motor Model Slip Frequency Gain
Program
Motor Parameters
Vector Motor Model
This parameter provides a degree of slip compensation for a given load. A
higher setting here decreases the slip allowed for a given load/ASD output ratio.
Direct Access Number — F401
Parameter Type —
Numerical
Factory Default —
0.60
Changeable During Run —
Yes
Minimum — 0.00
Maximum — 2.55
Motor Constant 1 (primary resistance)
Program
Motor Parameters
Vector Motor Model
This parameter is the measurement of the stator resistance and is considered a
Motor Constant
(unchanging). This value is used in conjunction with other
constants to tune the motor.
To use
Vector Control
,
Automatic Torque Boost
, or
Automatic Energy-
Saving
, the
Motor Constant
setting (motor tuning) is required.
Direct Access Number — F402
Parameter Type —
Numerical
Factory Default — (ASD dependent)
Changeable During Run —
No
Minimum — 0.0
Maximum — 100,000 M
Units —
Summary of Contents for HX7+ ASD
Page 2: ...DN 67017 001 February 2014 HX7 ASD Installation Operation Manual ...
Page 227: ...218 HX7 ASD Installation and Operation Manual Figure 35 200 kVA Sine Wave NEMA 1 Enclosure ...
Page 231: ...222 HX7 ASD Installation and Operation Manual Figure 39 200 kVA Sine Wave NEMA 3R Enclosure ...
Page 235: ...226 HX7 ASD Installation and Operation Manual Figure 43 66 163 kVA 18 Pulse Enclosure ...
Page 236: ...HX7 ASD Installation and Operation Manual 227 Figure 44 200 kVA 18 Pulse Enclosure ...
Page 237: ...228 HX7 ASD Installation and Operation Manual Figure 45 260 518 kVA 18 Pulse Enclosure ...
Page 238: ...HX7 ASD Installation and Operation Manual 229 Figure 46 518 700 kVA 18 Pulse Enclosure ...