74
HX7+ ASD Installation and Operation Manual
FM Terminal Adjustment
Program
Meter Terminal Adjustment
This function is used to calibrate the
FM
analog output terminal.
To calibrate the
FM
analog output, connect a meter (current or voltage) as
With the drive running at a known frequency, adjust this parameter (
) until
the running frequency produces the desired DC level output at the
FM
terminal.
Direct Access Number — F006
Parameter Type —
Numerical
Factory Default —
512
Changeable During Run —
Yes
Minimum — 0
Maximum — 1280
Type Reset
Program
Utility Parameters
This feature assists the user when performing fault analysis or by
allowing a quick system setup change when required. Performing a
Type Reset
results in one of the following user-selected post-reset
configurations.
Settings:
0 — None
1 — Auto Setup for 50 Hz
2 — Auto Setup for 60 Hz
3 — Restore Factory Defaults
4 — Clear Trip
5 — Clear Run Timer
6 — New Base Drive Board
7 — *Save User Parameters
8 — Restore User Parameters
9 — Reload EOI Flash (keypad)
10 — Reset EOI Memory (keypad)
Note:
*User settings that are stored in the memory of the keypad are
not saved via the
Save User Parameters
selection. The unsaved
functions include the
EOI Option Setups
, (Utility Parameters
Display Units
, and (Monitor Setup
)
Scrolling Monitor
.
Direct Access Number — F007
Parameter Type —
Selection List
Factory Default —
None
Changeable During Run —
No
Direction (of motor rotation)
No path available (Direct Access Only)
While operating using the
CN8 Option
(LED Keypad)
this parameter sets the
direction of motor rotation. This setting may be changed during operation.
This
setting
will not override parameter
(
Forward/Reverse Disable
).
If either direction is disabled via parameter
, the disabled direction will not
be recognized if commanded by the
CN8 Option
. If both directions are
, the direction command from the
CN8 Option
will
determine the direction of the motor rotation.
Settings:
0 — Forward
1 — Reverse
Note:
Press
ESC
screen to access the
Motor Direction parameter.
Direct Access Number — F008
Parameter Type —
Selection List
Factory Default —
Forward
Changeable During Run —
Yes
Reset
ve User
rameters
eset
Summary of Contents for HX7+ ASD
Page 2: ...DN 67017 001 February 2014 HX7 ASD Installation Operation Manual ...
Page 227: ...218 HX7 ASD Installation and Operation Manual Figure 35 200 kVA Sine Wave NEMA 1 Enclosure ...
Page 231: ...222 HX7 ASD Installation and Operation Manual Figure 39 200 kVA Sine Wave NEMA 3R Enclosure ...
Page 235: ...226 HX7 ASD Installation and Operation Manual Figure 43 66 163 kVA 18 Pulse Enclosure ...
Page 236: ...HX7 ASD Installation and Operation Manual 227 Figure 44 200 kVA 18 Pulse Enclosure ...
Page 237: ...228 HX7 ASD Installation and Operation Manual Figure 45 260 518 kVA 18 Pulse Enclosure ...
Page 238: ...HX7 ASD Installation and Operation Manual 229 Figure 46 518 700 kVA 18 Pulse Enclosure ...